Redacted Public Proposals for Current and Closed Windows


Proposal ID Target Zone Analysis Type Flowgates Project Description
768 AEP See Proposal See Proposal Axton - Joshua Falls - Mt Ida
12 PECO See Proposal See Proposal Competitive Window Upgrades
983 DOM See Proposal See Proposal 500kV Safety Solutions
17 PPL See Proposal See Proposal Bushkill - Kittatinny 230 kV line reconductor
533 ATSI See Proposal See Proposal Lemoyne - Lake Ave 345kV
72 PPL See Proposal See Proposal Juniata - Cumberland - Williams Grove 230 kV upgrade project
761 DOM See Proposal See Proposal J138/115 kV Safety Solutions
980 DOM See Proposal See Proposal Line #579 EOL Rebuild_Septa to Yadkin (99-2993)
312 PPL See Proposal See Proposal Acahela 500/230 kV Substation expansion project
330 PPL See Proposal See Proposal Juniata - Hunterstown 500 kV line
386 PPL See Proposal See Proposal Juniata - TMIS 500 kV DCT line
479 PPL See Proposal See Proposal Lackawanna - Paupack 230 kV line reconductor
526 PPL See Proposal See Proposal Jenkins - Pocono 230 kV line
549 PPL See Proposal See Proposal Susquehanna T10 Station Line Reconfiguration
850 PPL See Proposal See Proposal Pocono 80 MVAr 230 kV capacitor bank
860 PPL See Proposal See Proposal Face Rock T1 and T2 transformer replacement
24 DOM See Proposal See Proposal 230kV and 115kV Solutions for Portfolios
876 PPL See Proposal See Proposal Siegfried 500/230 kV Substation expansion project
922 PPL See Proposal See Proposal Lackawanna - Siegfried - Drakestown 500 kV line project
926 PPL See Proposal See Proposal Wescosville 2nd 500/138 kV transformer
935 PPL See Proposal See Proposal Juniata 500 kV Substation yard reconfiguration
390 DOM See Proposal See Proposal 230kV Safety Solutions
994 PPL See Proposal See Proposal Juniata - Dauphin 230 kV line reconductor
992 AEP/DOM See Proposal See Proposal Axton - Joshua Falls - Mt Ida 765kV transmission lines + Link 500/230kV substation
146 AEP/DOM See Proposal See Proposal Axton - Joshua Falls 765kV + Joshua Falls - Mt Ida 500kV
294 PPL See Proposal See Proposal Bay Shore - Davis-Besse - Lake Ave
357 AEP See Proposal See Proposal Bay Shore - Davis-Besse - Lake Ave + Lemoyne - Lake Ave 345kV
944 AEP/DOM See Proposal See Proposal Upgrades to AEP 138kV and Dominion 230kV transmission lines
873 DOM See Proposal See Proposal Line 8 Rebuild - Bremo to Scottsville Interconnection (APCO)
200 AEP/DOM See Proposal See Proposal Common Components
781 DOM See Proposal See Proposal 500kV Solutions for Portfolios
135 COMED See Proposal See Proposal Reconductor 345 kV lines 1202 & 1227 Dresden to Mulberry
447 COMED See Proposal See Proposal Cut 345 kV L8014 Pontiac to Dresden into Mulberry
967 DOM See Proposal See Proposal DVP Central Area Improvement for Portfolios
605 ATSI See Proposal See Proposal ATSI 138kV Rebuild + Substation Terminal Upgrades
502 APS See Proposal See Proposal Hunterstown #2 500/230 kV Transformer
843 ATSI See Proposal See Proposal Lemoyne - Lake Ave 345 kV Line
546 PPL/JCPL See Proposal See Proposal Pennsylvania Border - Drakestown 500 kV line (greenfield route)
900 PPL/JCPL See Proposal See Proposal Pennsylvania Border - Drakestown 500 kV line (brownfield route)
81 AEP See Proposal See Proposal Incumbent upgrades for Portfolio #1, 2 & 3
114 AEP/DOM/APS See Proposal See Proposal Joint Proposal
532 COMED See Proposal See Proposal 345kV Shunt Inductor at Mulberry
888 COMED See Proposal See Proposal Reconductor Des Plaines to Busse
816 COMED See Proposal See Proposal Autotransformer at Itasca
262 AEP/DOM/APS See Proposal See Proposal Joint Proposal
279 AEP/DOM/APS See Proposal See Proposal Joint Proposal
261 DOM See Proposal See Proposal Overdutied Breaker Replacement
527 DOM See Proposal See Proposal Cap Bank and STATCOM Installation
885 AEP/DOM/APS See Proposal See Proposal Components for Proposals 2024-W1-636, 610, 279 and 114
727 FE See Proposal See Proposal Kammer - 502 Junction 765 kV Line
977 APS See Proposal See Proposal Belmont - Harrison 500 kV Line
907 APS See Proposal See Proposal 500 kV Expansion Plan
232 APS See Proposal See Proposal FirstEnergy Upgrades to Support Portfolio Proposals
904 AEP/DOM/APS See Proposal See Proposal F1 Solution
955 PSEG See Proposal See Proposal 230kv Eagle Point - Penrose
132 PEPCO See Proposal See Proposal Dickerson H 230kV Caps
295 PEPCO See Proposal See Proposal Marley Neck 115 kV Substation
470 BGE See Proposal See Proposal GE local Mitigation Alternative
708 AEP/DOM/APS See Proposal See Proposal Amos - Welton Springs - Point of Rocks 765 kV Line
883 AEP/DOM/APS See Proposal See Proposal Amos - Welton Spring 765 kV Line
286 AEP/DOM See Proposal See Proposal Joshua Falls - Durandal
300 AEP/DOM See Proposal See Proposal Yeat - Vontay
350 AEP See Proposal See Proposal Jester - Hayden
167 AEP See Proposal See Proposal Leesville Station Conductor Replacement
738 AEP/DOM See Proposal See Proposal Boxwood-Bremo 138 kV Rebuild
949 AEP See Proposal See Proposal Boxwood-Bremo 138 kV Sag Study and Partial Rebuild
551 APS See Proposal See Proposal Chanceford - Goose Creek 500 kV Line
856 AEP See Proposal See Proposal Canal - Mound Street 138 kV Rebuild
769 AEP See Proposal See Proposal Rebuild Beatty-Cyprus 138 kV Line
464 AEP See Proposal See Proposal Genoa-Westar Sag Remediation
117 AEP See Proposal See Proposal Tidd-Mahans Lane 138 kV Rebuild
574 AEP See Proposal See Proposal Tiltonsville-West Bellaire 138 kV Rebuild
940 AEP See Proposal See Proposal Canal - Gay 138 kV Rebuild
622 AEP/DOM/APS See Proposal See Proposal F2 Solution
898 AEP/DOM/APS See Proposal See Proposal F3 Solution
124 AEP/DOM/APS See Proposal See Proposal F4 Solution
78 AEP/DOM/APS See Proposal See Proposal F5 Solution
506 AEP/DOM/APS See Proposal See Proposal F6 Solution
317 AEP/DOM/APS See Proposal See Proposal F7 Solution
839 AEP/DOM/APS See Proposal See Proposal F8 Solution
744 AEP See Proposal See Proposal Maliszewski-Polaris Rebuild
338 AEP See Proposal See Proposal Genoa-Westar Rebuild
276 AEP See Proposal See Proposal Bixby - Buckeye Steel 138 kV Reconfiguration
756 AEP See Proposal See Proposal Cyprus Station Reconfiguration
863 AEP See Proposal See Proposal Maliszewski Series Reactor Upgrades
408 AEP See Proposal See Proposal Maliszewski 765/345 kV Upgrades
610 AEP/DOM/APS See Proposal See Proposal Joint Proposal
459 AEP See Proposal See Proposal Mountaineer and Belmont Station Upgrades
617 AEP See Proposal See Proposal Incumbent upgrades for Portfolio #4
636 AEP/DOM/APS See Proposal See Proposal Joint Proposal
665 AEP/DOM See Proposal See Proposal Joshua Falls - Vontay - Morrisville South
694 AEP/DOM/APS See Proposal See Proposal Fostoria Central - Lake Ave. 345 kV DC
759 AEP/DOM/APS See Proposal See Proposal Joint Proposal
820 AEP/DOM See Proposal See Proposal Joshua Falls - Yeat

Proposal ID Target Zone Analysis Type Flowgates Project Description
367 Dominion End of Life Criteria 2023W2-DOM-O1 Line #588 Yadkin-Fentress EOL Rebuild
627 PSEG Thermal 2023W2-PSEG-T15, 2023W2-PSEG-T14, 2023W2-PSEG-T13, 2023W2-PSEG-T9, 2023W2-PSEG-T8, 2023W2-PSEG-T5, 2023W2-PSEG-T6, 2023W2-PSEG-T3, 2023W2-PSEG-T4, 2023W2-PSEG-T1, 2023W2-PSEG-T10, 2023W2-PSEG-T2 Jackson Road 230kV Station to Cedar Grove 230kV Station (5000kcmil cable)
998 PSEG Thermal 2023W2-PSEG-T15, 2023W2-PSEG-T14, 2023W2-PSEG-T13, 2023W2-PSEG-T9, 2023W2-PSEG-T8, 2023W2-PSEG-T5, 2023W2-PSEG-T6, 2023W2-PSEG-T3, 2023W2-PSEG-T4, 2023W2-PSEG-T1, 2023W2-PSEG-T10, 2023W2-PSEG-T2 69kV Circuit Reinforcement from Cedar Grove to Jackson Road
496 PSEG Thermal 2023W2-PSEG-T15, 2023W2-PSEG-T14, 2023W2-PSEG-T13, 2023W2-PSEG-T9, 2023W2-PSEG-T8, 2023W2-PSEG-T5, 2023W2-PSEG-T6, 2023W2-PSEG-T3, 2023W2-PSEG-T4, 2023W2-PSEG-T1, 2023W2-PSEG-T10, 2023W2-PSEG-T2 Jackson Road 230kV Station to Cedar Grove 230kV Station (3500kcmil cable)
716 PSEG Thermal 2023W2-PSEG-T15, 2023W2-PSEG-T14, 2023W2-PSEG-T13, 2023W2-PSEG-T9, 2023W2-PSEG-T8, 2023W2-PSEG-T5, 2023W2-PSEG-T6, 2023W2-PSEG-T3, 2023W2-PSEG-T4, 2023W2-PSEG-T1, 2023W2-PSEG-T10, 2023W2-PSEG-T2 Montville - Jackson Rd 230 kV line project
343 AEP Gen Deliv., Thermal 2023W2-N1-ST21, 2023W2-N1-ST20, 2023W2-N1-ST23, 2023W2-N1-ST22, 2023W2-N1-ST25, 2023W2-GD-S165, 2023W2-N1-ST24, 2023W2-N1-ST27, 2023W2-N1-ST26, 2023W2-N2-ST32, 2023W2-N1-ST19, 2023W2-N2-ST33, 2023W2-N2-ST30, 2023W2-N2-ST31, 2023W2-N2-ST38, 2023W2-N2-ST39, 2023W2-N2-ST36, 2023W2-N2-ST37, 2023W2-N2-ST34, 2023W2-N2-ST35, 2023W2-GD-S170, 2023W2-N1-ST10, 2023W2-N1-ST12, 2023W2-N1-ST11, 2023W2-N1-ST14, 2023W2-N1-ST13, 2023W2-N1-ST16, 2023W2-N1-ST15, 2023W2-N1-ST18, 2023W2-N1-ST17, 2023W2-N1-ST1, 2023W2-N2-ST21, 2023W2-N2-ST22, 2023W2-N1-ST3, 2023W2-N1-ST2, 2023W2-N2-ST20, 2023W2-N1-ST5, 2023W2-N1-WT1, 2023W2-N1-ST4, 2023W2-N1-ST7, 2023W2-N1-WT3, 2023W2-N1-ST6, 2023W2-N1-WT2, 2023W2-N2-ST29, 2023W2-N2-ST27, 2023W2-N2-ST28, 2023W2-N2-ST25, 2023W2-N2-ST26, 2023W2-N2-ST23, 2023W2-N2-ST24, 2023W2-GD-S4, 2023W2-GD-S3, 2023W2-GD-S186, 2023W2-N2-WT8, 2023W2-N2-WT7, 2023W2-N2-ST50, 2023W2-N2-WT6, 2023W2-N2-ST9, 2023W2-N2-WT5, 2023W2-N2-ST8, 2023W2-N2-WT4, 2023W2-N2-ST7, 2023W2-N2-WT3, 2023W2-GD-W154, 2023W2-GD-W155, 2023W2-GD-W153, 2023W2-GD-W156, 2023W2-GD-S115, 2023W2-GD-S114, 2023W2-N2-ST43, 2023W2-N2-ST44, 2023W2-N2-ST41, 2023W2-N2-ST42, 2023W2-N2-ST40, 2023W2-N2-ST49, 2023W2-N2-ST47, 2023W2-N2-ST48, 2023W2-GD-S6, 2023W2-N2-ST45, 2023W2-N2-ST46, 2023W2-GD-W162, 2023W2-GD-W165, 2023W2-GD-W163, 2023W2-GD-W164, 2023W2-GD-S122, 2023W2-GD-S121, 2023W2-GD-S123, 2023W2-GD-S126, 2023W2-GD-S125, 2023W2-GD-S116, 2023W2-GD-W59, 2023W2-GD-W58, 2023W2-N1-WT10, 2023W2-N1-WT13, 2023W2-N1-WT14, 2023W2-N1-WT11, 2023W2-N1-WT12, 2023W2-GD-W213, 2023W2-N2-ST6, 2023W2-N2-WT2, 2023W2-GD-W214, 2023W2-N2-ST5, 2023W2-N2-WT1, 2023W2-N2-ST4, 2023W2-N2-ST3, 2023W2-GD-S135, 2023W2-GD-W217, 2023W2-N2-ST2, 2023W2-N2-ST1, 2023W2-GD-W215, 2023W2-GD-W216, 2023W2-GD-S127, 2023W2-N1-ST9, 2023W2-N1-WT5, 2023W2-GD-S141, 2023W2-N1-ST8, 2023W2-N1-WT4, 2023W2-N1-WT7, 2023W2-N1-WT6, 2023W2-N1-WT9, 2023W2-N1-WT8, 2023W2-N2-ST11, 2023W2-N2-ST10, 2023W2-N2-ST17, 2023W2-N2-ST16, 2023W2-N2-ST19, 2023W2-N2-ST18, 2023W2-N2-ST13, 2023W2-N2-ST12, 2023W2-N2-ST15, 2023W2-N2-ST14, 2023W2-GD-W19, 2023W2-GD-W25 Jester - Hayden
27 AEP Gen Deliv., Thermal 2023W2-N1-ST21, 2023W2-N1-ST20, 2023W2-N1-ST23, 2023W2-N1-ST22, 2023W2-N1-ST25, 2023W2-GD-S165, 2023W2-N1-ST24, 2023W2-N1-ST27, 2023W2-N1-ST26, 2023W2-N2-ST32, 2023W2-N1-ST19, 2023W2-N2-ST33, 2023W2-N2-ST30, 2023W2-N2-ST31, 2023W2-N2-ST38, 2023W2-N2-ST39, 2023W2-N2-ST36, 2023W2-N2-ST37, 2023W2-N2-ST34, 2023W2-N2-ST35, 2023W2-N1-ST10, 2023W2-N1-ST12, 2023W2-N1-ST11, 2023W2-N1-ST14, 2023W2-N1-ST13, 2023W2-N1-ST16, 2023W2-N1-ST15, 2023W2-N1-ST18, 2023W2-N1-ST17, 2023W2-N1-ST1, 2023W2-N2-ST21, 2023W2-N2-ST22, 2023W2-N1-ST3, 2023W2-N1-ST2, 2023W2-N2-ST20, 2023W2-N1-ST5, 2023W2-N1-WT1, 2023W2-N1-ST4, 2023W2-N1-ST7, 2023W2-N1-WT3, 2023W2-N1-ST6, 2023W2-N1-WT2, 2023W2-N2-ST29, 2023W2-N2-ST27, 2023W2-N2-ST28, 2023W2-N2-ST25, 2023W2-N2-ST26, 2023W2-N2-ST23, 2023W2-N2-ST24, 2023W2-GD-S4, 2023W2-GD-S3, 2023W2-GD-S186, 2023W2-N2-WT8, 2023W2-N2-WT7, 2023W2-N2-ST50, 2023W2-N2-WT6, 2023W2-N2-ST9, 2023W2-N2-WT5, 2023W2-N2-ST8, 2023W2-N2-WT4, 2023W2-N2-ST7, 2023W2-N2-WT3, 2023W2-GD-W154, 2023W2-GD-W155, 2023W2-GD-W153, 2023W2-GD-W156, 2023W2-GD-S115, 2023W2-GD-S114, 2023W2-N2-ST43, 2023W2-N2-ST44, 2023W2-N2-ST41, 2023W2-N2-ST42, 2023W2-N2-ST40, 2023W2-N2-ST49, 2023W2-N2-ST47, 2023W2-N2-ST48, 2023W2-GD-S6, 2023W2-N2-ST45, 2023W2-N2-ST46, 2023W2-GD-W162, 2023W2-GD-W165, 2023W2-GD-W163, 2023W2-GD-W164, 2023W2-GD-S122, 2023W2-GD-S121, 2023W2-GD-S123, 2023W2-GD-S126, 2023W2-GD-S125, 2023W2-GD-S116, 2023W2-GD-W59, 2023W2-N1-WT10, 2023W2-N1-WT13, 2023W2-N1-WT14, 2023W2-N1-WT11, 2023W2-N1-WT12, 2023W2-N2-ST6, 2023W2-N2-WT2, 2023W2-GD-W214, 2023W2-N2-ST5, 2023W2-N2-WT1, 2023W2-N2-ST4, 2023W2-N2-ST3, 2023W2-GD-S135, 2023W2-GD-W217, 2023W2-N2-ST2, 2023W2-N2-ST1, 2023W2-GD-W215, 2023W2-GD-W216, 2023W2-GD-S127, 2023W2-N1-ST9, 2023W2-N1-WT5, 2023W2-GD-S141, 2023W2-N1-ST8, 2023W2-N1-WT4, 2023W2-N1-WT7, 2023W2-N1-WT6, 2023W2-N1-WT9, 2023W2-N1-WT8, 2023W2-N2-ST11, 2023W2-N2-ST10, 2023W2-N2-ST17, 2023W2-N2-ST16, 2023W2-N2-ST19, 2023W2-N2-ST18, 2023W2-N2-ST13, 2023W2-N2-ST12, 2023W2-N2-ST15, 2023W2-N2-ST14, 2023W2-GD-W19, 2023W2-GD-W25 Barron Transmission Project
117 AEP Gen Deliv., Thermal 2023W2-N1-ST21, 2023W2-N1-ST20, 2023W2-N1-ST23, 2023W2-N1-ST22, 2023W2-N1-ST25, 2023W2-GD-S165, 2023W2-N1-ST24, 2023W2-N1-ST27, 2023W2-N1-ST26, 2023W2-N2-ST32, 2023W2-N1-ST19, 2023W2-N2-ST33, 2023W2-N2-ST30, 2023W2-N2-ST31, 2023W2-N2-ST38, 2023W2-N2-ST39, 2023W2-N2-ST36, 2023W2-N2-ST37, 2023W2-N2-ST34, 2023W2-N2-ST35, 2023W2-N1-ST10, 2023W2-N1-ST12, 2023W2-N1-ST11, 2023W2-N1-ST14, 2023W2-N1-ST13, 2023W2-N1-ST16, 2023W2-N1-ST15, 2023W2-N1-ST18, 2023W2-N1-ST17, 2023W2-N1-ST1, 2023W2-N2-ST21, 2023W2-N2-ST22, 2023W2-N1-ST3, 2023W2-N1-ST2, 2023W2-N2-ST20, 2023W2-N1-ST5, 2023W2-N1-WT1, 2023W2-N1-ST4, 2023W2-N1-ST7, 2023W2-N1-WT3, 2023W2-N1-ST6, 2023W2-N1-WT2, 2023W2-N2-ST29, 2023W2-N2-ST27, 2023W2-N2-ST28, 2023W2-N2-ST25, 2023W2-N2-ST26, 2023W2-N2-ST23, 2023W2-N2-ST24, 2023W2-GD-S4, 2023W2-GD-S3, 2023W2-GD-S186, 2023W2-N2-WT8, 2023W2-N2-WT7, 2023W2-N2-ST50, 2023W2-N2-WT6, 2023W2-N2-ST9, 2023W2-N2-WT5, 2023W2-N2-ST8, 2023W2-N2-WT4, 2023W2-N2-ST7, 2023W2-N2-WT3, 2023W2-GD-W154, 2023W2-GD-W155, 2023W2-GD-W153, 2023W2-GD-W156, 2023W2-GD-S115, 2023W2-GD-S114, 2023W2-N2-ST44, 2023W2-N2-ST41, 2023W2-N2-ST42, 2023W2-N2-ST40, 2023W2-N2-ST49, 2023W2-N2-ST47, 2023W2-N2-ST48, 2023W2-GD-S6, 2023W2-N2-ST45, 2023W2-N2-ST46, 2023W2-GD-W162, 2023W2-GD-W165, 2023W2-GD-W163, 2023W2-GD-W164, 2023W2-GD-S122, 2023W2-GD-S121, 2023W2-GD-S123, 2023W2-GD-S126, 2023W2-GD-S125, 2023W2-GD-S116, 2023W2-GD-W59, 2023W2-N1-WT10, 2023W2-N1-WT13, 2023W2-N1-WT14, 2023W2-N1-WT11, 2023W2-N1-WT12, 2023W2-N2-ST6, 2023W2-N2-WT2, 2023W2-GD-W214, 2023W2-N2-ST5, 2023W2-N2-WT1, 2023W2-N2-ST4, 2023W2-N2-ST3, 2023W2-GD-S135, 2023W2-GD-W217, 2023W2-N2-ST2, 2023W2-N2-ST1, 2023W2-GD-W215, 2023W2-GD-W216, 2023W2-GD-S127, 2023W2-N1-ST9, 2023W2-N1-WT5, 2023W2-GD-S141, 2023W2-N1-ST8, 2023W2-N1-WT4, 2023W2-N1-WT7, 2023W2-N1-WT6, 2023W2-N1-WT9, 2023W2-N1-WT8, 2023W2-N2-ST11, 2023W2-N2-ST10, 2023W2-N2-ST16, 2023W2-N2-ST19, 2023W2-N2-ST13, 2023W2-N2-ST12, 2023W2-N2-ST15, 2023W2-N2-ST14, 2023W2-GD-W19, 2023W2-GD-W25 Vassell 765/345 kV Transformer Addition and Maliszewski Breaker Replacement
596 AEP Gen Deliv., Thermal 2023W2-GD-S186, 2023W2-GD-S141, 2023W2-N2-WT1, 2023W2-N2-ST4, 2023W2-N2-ST2, 2023W2-N1-ST15, 2023W2-N2-ST1, 2023W2-N2-ST30, 2023W2-N2-ST31, 2023W2-N2-WT4, 2023W2-N2-ST7, 2023W2-N2-ST28, 2023W2-N2-ST39, 2023W2-N2-ST37, 2023W2-N2-ST48, 2023W2-N2-ST46 Genoa-Westar Sag Remediation
561 AEP Gen Deliv. 2023W2-GD-S170, 2023W2-GD-S142, 2023W2-GD-W213, 2023W2-GD-W58 RP Mone-Maddox Creek Reconductor
957 AEP Gen Deliv., Thermal 2023W2-GD-S170, 2023W2-GD-S142, 2023W2-GD-W213, 2023W2-GD-W58 RP Mone-Maddox Creek Rebuild
729 AEP Gen Deliv., Thermal 2023W2-GD-S186, 2023W2-GD-S141, 2023W2-N2-WT1, 2023W2-N2-ST4, 2023W2-N2-ST2, 2023W2-N1-ST15, 2023W2-N2-ST1, 2023W2-N2-ST30, 2023W2-N2-ST31, 2023W2-N2-WT4, 2023W2-N2-ST7, 2023W2-N2-ST28, 2023W2-N2-ST39, 2023W2-N2-ST37, 2023W2-N2-ST48, 2023W2-N2-ST46 Genoa-Westar Rebuild
188 AEP Gen Deliv., Thermal 2023W2-N2-ST6, 2023W2-N2-ST5, 2023W2-N1-ST14, 2023W2-GD-S165, 2023W2-N1-ST13, 2023W2-N2-ST3, 2023W2-GD-S135, 2023W2-N2-ST32, 2023W2-N2-ST43, 2023W2-N2-ST22, 2023W2-N2-ST44, 2023W2-N2-ST40, 2023W2-N2-WT5, 2023W2-N2-ST8, 2023W2-N2-WT3, 2023W2-N2-ST17, 2023W2-N2-ST49, 2023W2-N2-ST18, 2023W2-N2-ST13, 2023W2-N2-ST25, 2023W2-N2-ST47, 2023W2-N2-ST24 Maliszewski-Polaris Reconductor
340 AEP Gen Deliv., Thermal 2023W2-N2-ST6, 2023W2-N2-ST5, 2023W2-N1-ST14, 2023W2-GD-S165, 2023W2-N1-ST13, 2023W2-N2-ST3, 2023W2-GD-S135, 2023W2-N2-ST32, 2023W2-N2-ST43, 2023W2-N2-ST22, 2023W2-N2-ST44, 2023W2-N2-ST40, 2023W2-N2-WT5, 2023W2-N2-ST8, 2023W2-N2-WT3, 2023W2-N2-ST17, 2023W2-N2-ST49, 2023W2-N2-ST18, 2023W2-N2-ST13, 2023W2-N2-ST25, 2023W2-N2-ST47, 2023W2-N2-ST24 Maliszewski-Polaris Rebuild
340 AEP Gen Deliv., Thermal 2023W2-N2-ST6, 2023W2-N2-ST5, 2023W2-N1-ST14, 2023W2-GD-S165, 2023W2-N1-ST13, 2023W2-N2-ST3, 2023W2-GD-S135, 2023W2-N2-ST32, 2023W2-N2-ST43, 2023W2-N2-ST22, 2023W2-N2-ST44, 2023W2-N2-ST40, 2023W2-N2-WT5, 2023W2-N2-ST8, 2023W2-N2-WT3, 2023W2-N2-ST17, 2023W2-N2-ST49, 2023W2-N2-ST18, 2023W2-N2-ST13, 2023W2-N2-ST25, 2023W2-N2-ST47, 2023W2-N2-ST24 Maliszewski-Polaris Rebuild
683 AEP Gen Deliv. 2023W2-GD-W12 Allen-RP Mone Sag Mitigations
169 AEP Gen Deliv. 2023W2-GD-W12 Allen-RP Mone Reconductor
819 AEP Gen Deliv. 2023W2-GD-W12 Allen-RP Mone Reconductor
11 AEP Gen Deliv. 2023W2-GD-S170, 2023W2-GD-S142, 2023W2-GD-W12, 2023W2-GD-W213, 2023W2-GD-W58 East Lima Phase Shifting Transformer
334 AEP Gen Deliv. 2023W2-GD-S170, 2023W2-GD-S142, 2023W2-GD-W12, 2023W2-GD-W213, 2023W2-GD-W58 Sorenson-Maddox Circuit Addition
426 AEP Gen Deliv. 2023W2-N2-ST50, 2023W2-N2-ST9, 2023W2-N2-ST16, 2023W2-N2-ST34, 2023W2-N2-ST45 Genoa-Spring Road Sag Mitigation
92 AEP Gen Deliv. 2023W2-N2-ST11, 2023W2-N2-ST41, 2023W2-N2-WT8, 2023W2-N2-ST10, 2023W2-N2-WT7, 2023W2-N2-ST36, 2023W2-N2-ST12, 2023W2-N2-ST23, 2023W2-N2-ST14 Polaris-Westar Rebuild

Proposal ID Target Zone Analysis Type Flowgate Project Description
35 ComEd Summer, Gen Deliv 2023W1-GD-S554, 2023W1-GD-S1259, 2023W1-GD-S571, 2023W1-GD-S563, 2023W1-GD-S1260, 2023W1-GD-S570, 2023W1-GD-S190, 2023W1-GD-S548 Reconductor 18.7 miles of 345 kV lines 11620 & 11622 from Elwood to Goodings Grove with two conductor bundled 1033.5 ACSS conductor. Modify and replace towers as necessary to accommodate the higher mechanical loads of the bundled conductor.
107 PSEG Light Load Voltage Mag 2023W1-N1-LLVM1, 2023W1-N1-LLVM23, 2023W1-N1-LLVM2, 2023W1-N1-LLVM24, 2023W1-N1-LLVM21, 2023W1-N1-LLVM3, 2023W1-N1-LLVM22, 2023W1-N1-LLVM4, 2023W1-N1-LLVM20, 2023W1-N1-LLVM9, 2023W1-N1-LLVM5, 2023W1-N1-LLVM6, 2023W1-N1-LLVM7, 2023W1-N1-LLVM8, 2023W1-N1-LLVM29, 2023W1-N1-LLVM27, 2023W1-N1-LLVM28, 2023W1-N1-LLVM25, 2023W1-N1-LLVM26, 2023W1-N1-LLVM12, 2023W1-N1-LLVM34, 2023W1-N1-LLVM13, 2023W1-N1-LLVM35, 2023W1-N1-LLVM10, 2023W1-N1-LLVM32, 2023W1-N1-LLVM11, 2023W1-N1-LLVM33, 2023W1-N1-LLVM30, 2023W1-N1-LLVM31, 2023W1-N1-LLVM18, 2023W1-N1-LLVM19, 2023W1-N1-LLVM16, 2023W1-N1-LLVM38, 2023W1-N1-LLVM17, 2023W1-N1-LLVM14, 2023W1-N1-LLVM36, 2023W1-N1-LLVM15, 2023W1-N1-LLVM37 Replace existing 230kV 50MVAR fixed shunt reactor with a 230kV 150MVAR variable shunt reactor. Replace existing 345kV 100MVAR fixed shunt reactor with a 345kV 150MVAR variable shunt reactor.
138 ComEd Summer, Gen Deliv 2023W1-GD-S554, 2023W1-GD-S1259, 2023W1-GD-S571, 2023W1-GD-S563, 2023W1-GD-S1260, 2023W1-GD-S570, 2023W1-GD-S190, 2023W1-GD-S548 Install two new 345 kV circuits from Elwood to Joliet for a distance of approximately 8 miles.
158 PENELEC Summer Individual Plant Test 2023W1-IPD-S24, 2023W1-IPD-S21, 2023W1-IPD-S20 Rebuild North Meshoppen - Mehoopany #2 115 kV Line
384 AEP Short Circuit 2023W1-SC-4 Replace the overdutied Olive 345kV circuit breaker "D" with a 5000A 63 kA circuit breaker. No steady state ratings or contingency changes are anticipated for this proposal.
500 ComEd Winter Gen Deliv 2023W1-GD-W229, 2023W1-GD-W955, 2023W1-GD-W988, 2023W1-GD-W945, 2023W1-GD-W993, 2023W1-GD-W268, 2023W1-GD-W972, 2023W1-GD-W1397, 2023W1-GD-W1387, 2023W1-GD-W946 Expand Haumesser Road substation. Extend the line 11323 West Dekalb tap 1.6 miles into Haumesser Road to create new line 9411 from Haumesser to West Dekalb. Expand West Dekalb to tie line 9411 from Haumesser Road to the existing line 8315 from Glidden. Reconductor/rebuild 10 miles of line 9411 and 6 miles of line 8315.
573 DPL Summer Individual Plant Test 2023W1-IPD-S10, 2023W1-IPD-S11, 2023W1-IPD-S18, 2023W1-IPD-S19, 2023W1-IPD-S16, 2023W1-GD-S765, 2023W1-IPD-S17, 2023W1-IPD-S14, 2023W1-IPD-S15, 2023W1-IPD-S12, 2023W1-IPD-S13, 2023W1-GD-S803, 2023W1-GD-S802, 2023W1-IPD-S29, 2023W1-GD-S158, 2023W1-IPD-S27, 2023W1-GD-S798, 2023W1-IPD-S28, 2023W1-GD-S1436, 2023W1-IPD-S26, 2023W1-IPD-S9, 2023W1-IPD-S8, 2023W1-IPD-S7, 2023W1-IPD-S6, 2023W1-IPD-S5, 2023W1-IPD-S4, 2023W1-IPD-S3, 2023W1-IPD-S2, 2023W1-IPD-S1 Reconductor Silver Run - Cedar Creek 230kV line. Upgrade bushing, disconnect, stranded bus, and rigid bus at Cedar Creek substation. Upgrade 1590 ACSR "Lapwing" jumper and disconnect at Silver Run substation.
605 APS Summer Gen Deliv 2023W1-GD-S499, 2023W1-GD-S500, 2023W1-GD-S501, 2023W1-GD-S87, 2023W1-GD-S89, 2023W1-GD-S80 This project assumes a previous award of Project #904 from the 2022 RTEP Window #3. This project enhances Project #904 by increasing the throughput of power by increasing the line conductor ampacity, and the attached terminal equipment. The enhanced conductor and terminal equipment will increase from 4000A to 5000A capacity.
663 ComEd Summer Gen Deliv 2023W1-GD-S554, 2023W1-GD-S1259, 2023W1-GD-S571, 2023W1-GD-S563, 2023W1-GD-S1260, 2023W1-GD-S570, 2023W1-GD-S190, 2023W1-GD-S548 The Elwood - Joliet 345kV transmission project consists of an approximately 4 mile double circuit 345kV transmission line from the Elwood Substation to the Joliet Substation.
712 ComEd Winter Gen Deliv 2023W1-GD-W229, 2023W1-GD-W955, 2023W1-GD-W988, 2023W1-GD-W945, 2023W1-GD-W993, 2023W1-GD-W268, 2023W1-GD-W972, 2023W1-GD-W1397, 2023W1-GD-W1387, 2023W1-GD-W946 Rebuild/reconductor 138 kV line 11323 from Haumesser Road to the H-452 tap.
746 PENELEC Summer Individual Plant Test 2023W1-IPD-S25, 2023W1-IPD-S23, 2023W1-IPD-S22 Rebuild North Meshoppen - Mehoopany #1 115 kV Line
771 ComEd Summer Gen Deliv 2023W1-GD-S641, 2023W1-GD-S663, 2023W1-GD-S642, 2023W1-GD-S662, 2023W1-GD-S1262, 2023W1-GD-S1263 Add three 345 kV circuit breakers to Cherry Valley substation.
831 APS Summer Gen Deliv 2023W1-GD-S499, 2023W1-GD-S500, 2023W1-GD-S501, 2023W1-GD-S87, 2023W1-GD-S89, 2023W1-GD-S80 Polecat Station is a 765/500kV Station that features a 765kV three-position ring bus and a 500kV three-position ring bus. The 765kV ring bus connects Belmont-Mountaineer 765kV, Kammer 765kV, and a new 2620MVA SE transformer. The 500kV ring bus connects the new 2620MVA SE transformer, Belmont 500kV, and Flint Run 500kV transmission lines. 765kV circuit breaker upgrades will be completed at Mountaineer Station to meet the required 5000A rating.
850 APS Summer Gen Deliv 2023W1-GD-S499, 2023W1-GD-S500, 2023W1-GD-S501, 2023W1-GD-S87, 2023W1-GD-S89, 2023W1-GD-S80 Install second 765/500 kV transformer (#6) with nameplate rating of 1080/1440/1800 MVA (ONAN/ONAF/ONAF), consisting of three single-phase transformers and a spare unit, in parallel with the existing Transformer #5. The loadability ratings of the new transformer #6 are 2351/3148/3600 SN/SE/SLD and 2754/3380/3600 WN/WE/WLD. Install 765 kV four-breaker ring bus and two 500 kV breakers. Replace 500 kV disconnect switches.
851 APS Summer Gen Deliv 2023W1-GD-S499, 2023W1-GD-S500, 2023W1-GD-S501, 2023W1-GD-S87, 2023W1-GD-S89, 2023W1-GD-S80 Cork 765kV greenfield substation facilitates the upgrade of FirstEnergy’s Belmont 765/500kV transformer while resolving Mountaineer equipment overduty, and concerns deriving from the existing three terminal line of Mountaineer – Belmont – Kammer 765kV.
903 APS Summer Gen Deliv 2023W1-GD-S499, 2023W1-GD-S500, 2023W1-GD-S501, 2023W1-GD-S87, 2023W1-GD-S89, 2023W1-GD-S80 Replace the Belmont 765/500 kV Transformer #5 with a new transformer bank with nameplate rating of 1500/2000/2500 MVA (ONAN/ONAF/ONAF), consisting of three single-phase transformers and a spare transformer. The loadability ratings of the new transformer are 3125/4000/4750 SN/SE/SLD and 3500/4250/4750 WN/WE/WLD. Replace 500 kV disconnect switches.
905 APS Summer Gen Deliv 2023W1-GD-S499, 2023W1-GD-S500, 2023W1-GD-S501, 2023W1-GD-S87, 2023W1-GD-S89, 2023W1-GD-S80 Add (2) 765kV breakers at Joshua Falls to create a 2-breaker ring with the transformer still connected off the bus. Remove CT and RTL limits to bring both 765kV lines up to the 3000A wavetrap rating. Construct new Yeat 765/500/230kV station near existing Bristers 500/230kV substation. This substation will have (10) 500kV breakers, (2) 765/500kV transformers, (2) 500/230kV transformers, (2) 230kV CB’s and (1) 765kV CB. Construct 135-mile single circuit 765kV greenfield line connecting Joshua Falls 765kV and new Greenfield Yeat 765kV stations. Cut in Bristers–Ox 500kV and Meadowbrook–Vint Hill 500kV lines into Yeat’s 500kV yard. AEP installs a new 12-mile dbl ckt BOLD (Breakthrough Overhead Line Design) 230kV line from Yeat–CloverHIll. Dominion installs a new 7.5-mile dbl ckt BOLD (Breakthrough Overhead Line Design) 230kV line from Warrenton–Wheeler. Dominion installs new 0.1% reactor at Vinthill on Vinthill–Morrisville. Dominion Install new 0.1% reactor at Vinthill on Vinthill–Loudoun 1. Dominion Rebuilds 1.7 miles 230kV line from Marsh Run–RemingtonCt as double circuit. Dominion replaces remote end equipment to bring rating up on 230kV line from Wheeler–Linton Tap–Atlantic. Dominion rebuilds the 0.23-mile line between Bristers 500kV and Yeat 500kV. Dominion installs (2) 230kV breakers at Wheeler substation.
929 DLCO Light Load Gen Deliv 2023W1-GD-LL905, 2023W1-GD-LL550 Reconductor the limiting segments of the DLC-owned portion of the Cheswick-Wycoff Tap segment of the Cheswick-Yukon (Z-65) 138 kV tie-line (approximately 1.5 miles).
937 ComEd Summer Gen Deliv 2023W1-GD-S554, 2023W1-GD-S1259, 2023W1-GD-S571, 2023W1-GD-S563, 2023W1-GD-S1260, 2023W1-GD-S570, 2023W1-GD-S190, 2023W1-GD-S548 Apply conductor coating to lines 11620 & 11622 from Elwood to Goodings Grove. The coating increases emissivity and reduces absorptivity of the conductor, allowing for increased ratings. This technology was presented at PJM's Emerging Technology Forum on 3/17/21.
972 >ComEd Winter Gen Deliv 2023W1-GD-W229, 2023W1-GD-W955, 2023W1-GD-W988, 2023W1-GD-W945, 2023W1-GD-W993, 2023W1-GD-W268, 2023W1-GD-W972, 2023W1-GD-W1397, 2023W1-GD-W1387, 2023W1-GD-W946 Rebuild 138 kV line 11323 as double circuit from Haumesser Road to the H-452 tap and string a second circuit. Expand Haumesser Road to a 4 circuit breaker ring bus. Add a circuit breaker at H-452 to create a second path between Haumesser Road and Waterman.

Proposal ID Target Zone Analysis Type Flowgate Project Description
9 AEP/DOM See Proposal for Information See Proposal for Information

AEP proposes performing a sag study on the AEP-owned line section between Scottsville and Bremo 138 kV to identify and mitigate any clearance issues in order to operate at or above the identified line loadings.

23 DOM See Proposal for Information See Proposal for Information

This proposal incorporates construction of multiple transmission lines and substation expansions to provide a robust, expandable transmission solution to address the 2022 Open Window 3 violations. This proposal will also ensure the PJM transmission system can safely and reliably accommodate future load growth.

NOTE: The proposing entity has worked closely with other PJM TOs in developing a transmission solution and this proposal should be reviewed in conjunction with proposal 2022-W3-129 and proposal 2023-W3-660.

Subsequent to execution of the DEA for one or more of these projects, the proposing entity may file application with the FERC for award of the CWIP and abandonment transmission rate incentives that are typical for projects of this size.

24 MAAC See Proposal for Information See Proposal for Information

North Delta - New Raphael - Waugh Chapel 500kV

28 MAAC See Proposal for Information See Proposal for Information

New Pike 500/138 kV substation + SVC + Cap Banks, new Black Oak - Gore - Goose Creek 500 kV line, New Hunterstown-Doubs-Goose Creek 500 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured on component 10C2.

See attachment 1 for flowgate information.

30 DOM See Proposal for Information See Proposal for Information

This project serves to wreck/rebuild segment one of 230kV line 2054, demarcation point between Charlottesville Substation to Profitt D.P. using double-circuit capable 230 kV poles. The line will be rebuilt with 3-phase 2-768 ACSS Maumee Type 13 bundled conductor and two (2) DNO-11410 shield wire. Switches and line lead at Charlottesville substation will be upgraded to 4000A.

Upgrading line #2054, causes an overload on lines #233 and #291 under Summer Generator Deliverability study for the loss of line #553. This overload can happen by adding some new loads in Louisa area as well. By wrecking and rebuilding lines #233 and #291 using (2) 768.2 ACSS/TW (20/7) “MAUMEE” conductor with 3948A ampacity, 1573MVA, and upgrading the ratings of substation equipment at Charlottesville, Crozet, Barracks Rd, Hydraulic Rd and Dooms, the overload is mitigated.

55 AEP See Proposal for Information See Proposal for Information

AEP proposes rebuilding the line sections between Boxwood and Scottsville 138 kV in order to increase the emergency rating above the identified thermal overloads.

74 DOM See Proposal for Information See Proposal for Information

Wreck and rebuild line #2090 (Ladysmith CT to Fredericksburg) as a double circuit 230kV line using (2) 768.2 ACSS/TW (20/7) “MAUMEE” conductor with 3948A ampacity, 1573MVA. Only one circuit will be wired at this stage. Second circuit will be used for either rebuilding and conversion of line #47 or adding a new 230kV line if required. Upgrade circuit breaker leads, switches and line leads at Ladysmith CT and Fredericksburg, and upgrade circuit breakers at Fredericksburg.

116 DOM See Proposal for Information See Proposal for Information

New Gant 500/230 kV substation, New Hunterstown - Doubs - Gant 500 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in Component 40X.

See attachment 1 for flowgate information.

125 PSEG See Proposal for Information See Proposal for Information

North Delta-Northeast 230kV, reconductor Brandon Shore to Waugh Chapel

129 DOM See Proposal for Information See Proposal for Information

This proposal is a comprehensive package of all of Dominion Energy's solutions for the 500 kV violations identified under the 2027 Summer High Load Growth (HLG) Case scenario of PJM's Data Center Planning Initiative. The Package includes the following Projects:

  • 1. Interregional Solution - Aspen-Doubs (Refer to PJM ID 2022-W3-516)
  • 2. Regional Solution - 500 kV Wishing Star-North Anna Upgrade (Refer to PJM ID 2022-W3-711)
  • 3. Data Center Alley Local solution - New 500 kV/230 kV Aspen-Golden & Golden-Mars lines (Refer to PJM ID 2022-W3-692)
  • 4. Second 500 kV Line from Lexington to Dooms (Refer to PJM ID 2022-W3-923)
  • 5. Line #541 (Front Royal to Morrisville) Rebuild (Refer to PJM ID 2022-W3-671)
  • 6. Reactive Power VAR Reinforcements (Refer to PJM ID 2022-W3-231)
175 DOM See Proposal for Information See Proposal for Information

This proposal is a combination of multiple other solutions to deliver an overall complete solution. C

Combination of:

  • PEBO 215A (2022-W3-948)
  • WOP 1F (2022-W3-853)
  • SOP 8E (2022-W3-663)
  • Various brownfield components required to meet reliability needs
181 AEP See Proposal for Information See Proposal for Information

AEP proposes performing a sag study on the line sections between Boxwood and Scottsville 138 kV to identify and mitigate any clearance issues in order to operate above the identified line loadings.

196 AEP See Proposal for Information See Proposal for Information

Rebuild the double circuit 138kV line from Glen Lyn station to Peter Mountain station at roughly 3.6 miles. The current line from Glen Lyn to Peters Mountain is sag derated to 205 MVA in the Summer case. To mitigate the overload, the Summer emergency rating needs to be 214 MVA or above.

202 AEP See Proposal for Information See Proposal for Information

AEP proposes to establish a new 500/345 kV, 1500 MVA transformer and a new breaker string consisting of two new 500 kV circuit breakers, located in the Cloverdale 500 kV yard. A new 345 kV tie-line between the 500 kV yard and 345/138 kV yards will be required. In addition, a new 345 kV breaker string and two new 345 kV circuit breakers will be required in the 345/138 kV yard.

211 DOM See Proposal for Information See Proposal for Information

This project serves to wreck/rebuild segment one of 230kV line 2135, demarcation point between Holly Meade Junction (Str.339B) and Gordonsville using double-circuit capable 500/230 kV poles. The line will be rebuilt with 3-phase 2-768 ACSS Maumee Type 13 bundled conductor and two (2) DNO-11410 shield wire. Switches and line lead at HollyMead will be upgraded to 4000A.

217 DOM See Proposal for Information See Proposal for Information

New North Delta 500/23 kV substation, New North Delta - Conastone 500 kV line, plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured on component 26A.

See attachment 1 for flowgate information.

229 PSEG See Proposal for Information See Proposal for Information

Hunterstown-New Green Valley 500kV

231 DOM See Proposal for Information See Proposal for Information

Install 230KV/500kV shunt cap banks (static devices) as well as STATCOMs (dynamic devices) and associated equipment to address the reactive power needs of the system

234 AEP See Proposal for Information See Proposal for Information

Sag study the 138kV circuit from Glen Lyn station to Peter Mountain station at roughly 3.6 miles. The current line from Glen Lyn to Peters Mountain is sag derated to 205 MVA in the Summer case. To mitigate the overload, the Summer emergency rating needs to be 214 MVA or above.

255 DOM See Proposal for Information See Proposal for Information

New Gant 500 kV substation, New Hunterstown - Doubs - Gant 500 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in component 40X.

See attachment 1 for flowgate information.

279 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, new Black Oak - Woodside - Goose Creek 500 kV line, plus various modifications to existing substations

Proposal permitting and overhead costs are captured on component 10C2.

See attachment 1 for flowgate information.

325 PSEG See Proposal for Information See Proposal for Information

Brambleton-Hinsons Ford Rd 500kV

344 PECO See Proposal for Information See Proposal for Information

This proposal has been designed to 1) bring the significant generation interconnected at or near PECO’s Peach Bottom substation through the BGE territory 2) direct the power flow around BGE’S territory toward High Ridge substation in the west and Riverside substation in the east to aid in sending power towards the new load areas and 3) provide reactive support in PEPCO with a new STATCOM at Brighton amongst other upgrades and 4) enhance the existing FirstEnergy, PEPCO and Dominion seam through a collaboratively developed Joint Proposal. In particular, the Joint Solution between PEPCO, Dominion, and FirstEnergy rebuilds the Doubs to Goose Creek corridor to allow for an additional 500kV line from Doubs to Goose Creek and an additional 230kV circuit from Dickerson Station H to Ed’s Ferry.  Exelon MidAtlantic has developed West Cooper Max, including the Joint Solution, to not only compliment Dominion’s and FirstEnergy’s proposals (PJM proposal ids 2022-W3-129 & 2022-W3-129, but the Exelon MidAtlantic, Dominion, and FirstEnergy proposals together are designed to address all the PJM identified flow-gate violations in the three collective zones. Notwithstanding the collaboration, the West Cooper Max proposal maximizes the use of Exelon MidAtlantic’s existing transmission right-of-way such that of the 120+ miles of new or rebuilt transmission facilities envisioned for proposal, there is less than 2 miles of new ROW needed. Essentially, 98.3% of the new or rebuilt transmission facilities within this proposal is within existing ROW. This new ROW, primarily in the PECO zone is adjacent to existing Exelon owned transmission lines and substations near Cooper and Peach Bottom. Separately, this option does come with one alternative approach for establishing three (3) 500kV paths from Peach Bottom area toward BGE footprint.

347 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, new Black Oak - Woodside - Gant 500 kV line, Gant 500 kV substation, plus various modifications to existing substations

Proposal permitting and overhead costs are captured on component 4CA.

See attachment 1 for flowgate information.

374 PPL See Proposal for Information See Proposal for Information

Construct a new Otter Creek 500 kV 3-breaker Switching Station and bring the Three Mile Island - Peach Bottom 500 kV line in and out of the new switching station. Construct a new 500 kV line from the new Otter Creek 500 kV Switching Station to the existing Conastone 500 kV Substation.

385 DOM See Proposal for Information See Proposal for Information

The muddy creek portion of PEBO 220 scope can be energized in 2027 to incrementally meet PJM reliability needs. See schedule for more information.

New 12-terminal 500/230kV Bartholow substation with 6-terminal 500kV and 6-terminal 230kV, two 500/230kV transformers, two cap banks, and SVC. Interconnected with 500kV Doubs, Conastone, Brighton double circuit, Goram, and interconnected with 230kV Mt. Airy, double circuit Conastone, double circuit Grisham, and Otter Creek. New 230kV double circuit Bartholow to Conastone transmission line, new 230kV double circuit Bartholow to Grisham transmission line, and new 230kV Bartholow to Otter Creek transmission line. New 500kV Bartholow to Goram 500kV transmission line. New 3-terminal 500/230kV Goram substation with one 500/230kV transformer, interconnected with 500kV TMI, Peach Bottom, and Bartholow substations, and interconnected with 230kV Otter Creek substation. New 230kV Goram to Otter Creek transmission line. New 8-terminal 230kV Grisham substation with two cap banks and SVC, interconnected with 230kV Nimbus, Buttermilk, Pacific, BECO, and double circuit Bartholow. New 6-terminal 500/230kV North Delta substation with two 500/230kV transformers, interconnected with 500kV Delta York, Peach Bottom, and Conastone, and interconnected with 230kV Cooper and double circuit Graceton. New 500kV North Delta to Conastone transmission line. New 230kV double circuit North Delta to Graceton transmission lines and new 230kV North Delta to Cooper transmission line. Upgrade limiting elements of lines connecting North Peach Bottom and South Peach Bottom 500kV to achieve required rating.

Proposal permitting and overhead costs are captured in Component 26A.

See attachment 1 for flowgate information.

410 AEP See Proposal for Information See Proposal for Information

AEP proposes to establish a new 500 kV breaker position for the low-side of the existing 765/500 kV transformer at Cloverdale Station. The new position will be between two new 500 kV circuit breakers located in a new breaker string, electrically converting the 500 kV yard to "double-bus double-breaker" configuration.

419 DOM See Proposal for Information See Proposal for Information

New Hunterstown - Doubs - Audobon - Goose Creek 500 kV line, New BAudobon 500/230 kV substation, New Beaumeade - Paragon/Nimbus DCT 230 kV, plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured on component 21B.

See attachment 1 for flowgate information.

445 DOM See Proposal for Information See Proposal for Information

New Muddy Creek 230 kV switchyard, New Muddy Creek - Conastone/Graceton 230 kV lines, New North Delta 500/230 kV substation, New North Delta - Conastone 500 kV line, New Hunterstown - Doubs - Goose Creek 500 kV line plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured on component 21B.

See attachment 1 for flowgate information.

477 AEP See Proposal for Information See Proposal for Information

AEP proposes rebuilding the 138 kV double circuit line section between Fieldale and Franklin Substations

487 MAAC See Proposal for Information See Proposal for Information

Tie-line Impact Info: The proposal topology connects equipment owned by more than one Transmission Owner, in this case APS, BGE, MetEd, PenElec, PECO, PEPCO, and PPL (all PJM members).

This Proposed Solution (PS) is an enhanced version of Project 9A, which includes the Independence Energy Connection (IEC) Project. The PS consists of: (1) IEC West, which is comprised of approximately 29-miles of new double-circuit 230kV AC overhead transmission line between the existing Potomac Edison Ringgold Substation in Washington County, Maryland to a new Rice Substation in Franklin County, Pennsylvania; (2) reconfigured IEC East, is primarily comprised of adding 230kV AC overhead transmission lines between a new Furnace Run Substation in York County, Pennsylvania, and the existing BGE Conastone (via Baltimore County) and Graceton Substations in Harford County, Maryland; and (3) other incumbent work as described in the PS. The combination of these three elements provides a comprehensive solution for the current requirements in the area.

Four documents are attached to show the progress already made on this PS:

  • - JOINT AMENDED APPLICATION OF TRANSOURCE PENNSYLVANIA LLC AND PPL ELECTRIC UTILITIES CORPORATION (Attachment 1)
  • - MARYLAND ORDER APPROVING SETTLEMENT AND GRANTING CERTIFICATE OF PUBLIC CONVENIENCE AND NECESSITY AND WAIVERS (Attachment 2)
  • - LETTER ORDER GRANTING GBE GOOD CAUSE WAIVER (Attachment 3)
  • - MD ORDER GRANTING CPCN FOR RINGGOLD TO CATOCTIN UPGRADES (Attachment 4)

The PS will create new tie-lines between PENELEC (Area 226), METED (Area 227), and APS (Area 201), and also create new tie-lines between PECO (Area 230), METED (Area 227), PPL (Area 229), and BGE (Area 232).

516 DOM See Proposal for Information See Proposal for Information

Build a new 500 kV circuit between Aspen and Doubs - this project scope only accounts for construction up to the Doubs Interconnection Point, FirstEnergy/PEPCO will be responsible for building the remaining portion of the line to the Doubs substation. The Exelon proposals will be 2022-W3-660 and 2022-W3-344. The First Energy proposal (Potomac Edison Company) ID will be 2022-W3-837. 230kV Line #203 will be wrecked and rebuilt as a double circuit in the existing ROW to accommodate the new 500 kV line. Additionally, existing 500kV Line #514 will also be wrecked and rebuilt as a double circuit 500kV/230KV lines between Goose Creek/Pleasant View and the Doubs Interconnection Point. 230kV Line #2098 will share the double circuit between Pleasant View and Hamilton Substations, and the remaining portion will be built to accommodate a future 230 kV circuit. Substation equipment will be upgraded to accommodate impact of new lines and line modifications. Substation scope also includes overdutied breaker replacements at Pleasant View, Loudoun and Ox substations.

524 AEP See Proposal for Information See Proposal for Information

Install a 5% reactor at Opossom Creek on the Opossum Creek-Redeye 138 kV line and a 5% reactor at New London on the New London-Altavista 138 kV line.

530 DOM See Proposal for Information See Proposal for Information

New Muddy Creek 230 kV switchyard, New Muddy Creek - Conastone / Graceton 230 kV lines, New North Delta 500 kV switchyard, New North Delta - Conastone 500 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in component 25B.

See attachment 1 for flowgate information.

537 AEP See Proposal for Information See Proposal for Information

AEP proposes performing a sag clearance study to increase the summer emergency rating above the reported loadings for the Fieldale-Thornton and Thornton-Franklin line sections. Preliminary review using existing LiDAR data for that line recommends replacement of ferrous clamp hardware at each structure.

548 DOM See Proposal for Information See Proposal for Information

A large scale set of projects that solve the growing congestion issues in the southern Pennsylvania/northern Virginia/Maryland/West Virginia area. The project involves strategic rebuilds, substation upgrades, and greenfield transmission lines that primarily follow existing corridor. This strategic use of existing corridor greatly reduces the risk of projects being delayed due to opposition.

564 MAAC/DOM See Proposal for Information See Proposal for Information

New 10-terminal 500/230kV Bartholow substation with 4-terminal 500kV and 6-terminal 230kV, two 500/230kV transformers, two cap banks, and SVC. Interconnected with 500kV Doubs, Brighton, Goram, and interconnected with 230kV Mt. Airy, double circuit Conastone, double circuit Grisham, and Otter Creek. New 230kV double circuit Bartholow to Conastone transmission line, new 230kV double circuit Bartholow to Grisham transmission line, and new 230kV Bartholow to Otter Creek transmission line. New 500kV Bartholow to Goram 500kV transmission line. New 3-terminal 500/230kV Goram substation with one 500/230kV transformer, interconnected with 500kV TMI, Peach Bottom, and Bartholow substations, and interconnected with 230kV Otter Creek substation. New 230kV Goram to Otter Creek transmission line. New 8-terminal 230kV Grisham substation with two cap banks and SVC, interconnected with 230kV Nimbus, Buttermilk, Pacific, BECO, and double circuit Bartholow. New 6-terminal 500/230kV North Delta substation with two 500/230kV transformers, interconnected with 500kV Delta York, Peach Bottom, and Conastone, and interconnected with 230kV Cooper and double circuit Graceton. New 500kV North Delta to Conastone transmission line. New 230kV double circuit North Delta to Graceton transmission lines and new 230kV North Delta to Cooper transmission line. Upgrade limiting elements of lines connecting North Peach Bottom and South Peach Bottom 500kV to achieve required rating. Upgrade limiting elements of 500kV line between Conastone and Brighton to achieve required rating.

Proposal permitting and overhead costs are captured on component 26A.

See attachment 1 for flowgate information.

577 DOM See Proposal for Information See Proposal for Information

New Racefield 500kV switchyard, New Racefield - Front Royal 500 kV line, New Warrenton - Wheeler DCT 230 kV line, New North Anna - Lady Smith 230 kV line, plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured in Component 1B.

See attachment 1 for flowgate information.

598 DOM See Proposal for Information See Proposal for Information

This proposal is a combination of multiple other solutions to deliver an overall complete solution.

Combination of:

  • PEBO 220 (2022-W3-385)
  • WOP 1F (2022-W3-853)
  • SOP 8E (2022-W3-663)

Various brownfield components required to meet reliability needs

600 PECO See Proposal for Information See Proposal for Information

This proposal focuses primarily on replacing overloaded assets within PECO, BGE, and PEPCO on an asset-by-asset basis (e.g. reconductoring existing lines, replacing terminal equipment, etc.). These upgrades will provide incremental transmission capacity throughout the Exelon MidAtlantic territory and each upgrade within this proposal can be additive to both Exelon MidAtlantic and non-Exelon MidAtlantic proposals that PJM may be considering. The Replacement Upgrades require no new right-of-way.

606 PPL See Proposal for Information See Proposal for Information

Construct a new 32-mile Juniata - Lewistown 230 kV # 2 line by utilizing the existing brownfield 69 kV line route between Juniata and Mifflintown, and then building a greenfield line from Mifflintown to Lewistown. Build a new 2 breaker bay in the double bus double breaker Juniata 230 kV yard (note that today Juniata 230 kV is in a radial bus design, but the Juniata double bus double breaker upgrade is an existing PPL Supplemental Project {S0945.1} separate from this proposal). Build a new 2 breaker bay in the existing double bus double breaker Lewistown 230 kV yard.

629 AEP See Proposal for Information See Proposal for Information

Rebuild the 7.5 mile long portion of the AEP-owned section of the Scottsville-Bremo 138 kV line.

631 DOM See Proposal for Information See Proposal for Information

New Muddy Creek 230 kV switchyard, New Muddy Creek - Conastone/Graceton 230 kV lines, New North Delta 500/230 kV substation, New North Delta - Conastone 500 kV line, plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured in Component 25B.

See attachment 1 for flowgate information.

637 PSEG/APS See Proposal for Information See Proposal for Information

Conastone-Doubs 500kV

642 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, New Gant 500/230 kV substation, New 502 Junction - Black Oak - Woodside - Gant 500 kV line, New 230 kV line from Gant - Farmwell, New Cochran Tap - Round Table 230 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in Component 4CA.

See attachment 1 for flowgate information.

660 MAAC See Proposal for Information See Proposal for Information

BGE and PEPCO portions of West Cooper Solution (Exelon-full solution).

663 DOM See Proposal for Information See Proposal for Information

New Racefield 500kV switchyard, New Racefield - Front Royal 500 kV line, New Warrenton - Rixlew 230 kV line, New Warrenton-Hourglass 230 kV line, New Mars - Ocean Court-Davis Drive 230 kV line, plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured on component 1B.

See attachment 1 for flowgate information.

671 DOM See Proposal for Information See Proposal for Information

This project addresses overloads on Line #541, identified under the Prelim 2028 RTEP cases for 2022W3 (the new Generator Deliverability as well as N-1 study), by rebuilding approximately 47 miles of the transmission line form Front Royal to Morrisville substation to current 500 kV standards. The new conductor will have a minimum normal summer rating of 4357 MVA. Substation equipment, at Morrisville and Front Royal, will be upgraded to support the new conductor rating.

676 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, new Black Oak - Woodside - Gant 500 kV line, Gant 500/230 kV substation, New 230 kV line from Gant - Farmwell, New Cochran Tap - Round Table 230 kV line, plus various modifications to existing substations.

Proposal permitting and overhead costs are captured on component 4CA.

See attachment 1 for flowgate information.

685 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, New Fort Martin - Black Oak - Woodside 500 kV line plus various modifications to existing substations.

Proposal permitting and overhead costs are captured in Component 10C2.

See attachment 1 for flowgate information.

691 MAAC See Proposal for Information See Proposal for Information

Exelon is proposing a 230 mile, 500 kV AC / 400 kV DC high-voltage transmission line originating in Northern Virginia, crossing Maryland, traveling up the Delmarva Peninsula and terminating in southern New Jersey.

692 DOM See Proposal for Information See Proposal for Information

This proposal is a robust, holistic, and expandable solution to address the reliability needs in the Northern Virginia Data Center Alley (Local constraints). The proposal will include the following components:

  • 1. Installing new double-circuit 500/230 kV lines from Golden substation to Mars substation, and from Aspen substation to Golden Substation.
  • 2. Installing the second 500-230 kV, 1440 MVA transformer at Mars Substation.
  • 3. Upgrading existing double-circuit 230 kV lines from Golden substation to Paragon Park substation (Lines # 2150 & 2081), as well as an existing single circuit 230 kV line from Paragon Park substation to Beco Substation (Line # 2207) to a minimum normal summer rating of 1573 MVA. Equipment at each substation will be upgraded to support the new conductor rating of 4000A.
  • 4. Replacing overdutied breakers at Belmont, Beco, Beaumeade, Pleasant View, Shellhorn, and Discovery.
704 DOM See Proposal for Information See Proposal for Information

This project serves to wreck/rebuild segment one of 230kV line 2135, demarcation point between Holly Meade Junction (Str.339B) and Gordonsville using double-circuit capable 230 kV poles. The line will be rebuilt with 3-phase 2-768 ACSS Maumee Type 13 bundled conductor and two (2) DNO-11410 shield wire. Switches and line lead at HollyMead will be upgraded to 4000A.

711 DOM See Proposal for Information See Proposal for Information

This proposal is a comprehensive solution to add new 500 kV Transmission Lines from North Anna substation to Wishing Star Substation (North Anna-Spotsylvania-VintHill-Wishing Star). The proposal will include the following components:

  • 1. Building a new single circuit 500 kV line parallel to existing line #573 from North Anna Substation to Spotsylvania Substation.
  • 2. Wrecking and rebuilding both the 5-2 towers in the Morrisville-Loudoun-Brambleton corridor and free up space for adding one new single-500kV monopole within the same corridor. The new over-head 500kV lines will be from Spotsylvania to VintHill, and VintHill to Wishing Star in the existing ROW with current 500 kV Standards.
  • 3. Uprating Line #535 from structure 389 (First Energy Demarcation Point) to the point joining Morrisville-Loudoun corridor to current 500 kV Standards.
719 DOM See Proposal for Information See Proposal for Information

New Pike 500/138 kV substation + SVC + Cap Banks, New Fort Martin - Black Oak - Pike 500 kV line plus various modifications to existing substations.

Proposal permitting and overhead costs are captured in component 10C2.

See attachment 1 for flowgate information.

728 DOM See Proposal for Information See Proposal for Information

New Bartholow 500 kV Switchyard, New Barnhart500 kV Switchyard, New 500 kV line from Barnhart -Bartholow - Goose Creek, plus various modifications to existing lines and substations.

All of the permitting costs and overhead costs for this proposal are captured in component 38A.

See attachment 1 for flowgate information.

731 DOM See Proposal for Information See Proposal for Information

Locks 230/115 kV transformer TX #7 gets overloaded under Gen Deliv in RTEP 2027 HG case. Therefore, this project replaces TX #7 with new three phase transformers that have a higher rating of 224 MVA. Lead lines at the 115 kV level will be upgraded to 2000 A.

741 MAAC See Proposal for Information See Proposal for Information

500kV Greenfield line from Peach Bottom Station to Brandon Shores Station
500kV Greenfield line from Doubs Station to Peach Bottom Station
Reconductor 230kV Line from Brandon Shores Station to Waugh Chapel Station

766 DOM See Proposal for Information See Proposal for Information

New Racefield 500kV switchyard, New Racefield - Front Royal 500 kV line, New Warrenton - Wheeler DCT 230 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in Component 1B.

See attachment 1 for flowgate information.

808 MAAC See Proposal for Information See Proposal for Information

500kV Greenfield line from Peach Bottom to New Raphael Station, 500kV Greenfield line from New Raphael Station to Waugh Chapel, 500kV Greenfield line from Doubs Station to Peach Bottom Station, and a reconductor of Peach Bottom North to Peach Bottom South Tie #1 and #2

837 APS See Proposal for Information See Proposal for Information

This proposal incorporates construction of multiple transmission lines and substation expansions to provide a robust, expandable transmission solution to address the 2022 Open Window 3 violations. This proposal will also ensure the PJM transmission system can safely and reliably accommodate future load growth.

NOTE: The proposing entity has worked closely with other transmission owners in developing a transmission solution and this proposal should be reviewed in conjunction with proposal 2022-W3-129 and proposal 2023-W3-660.

Subsequent to execution of the DEA for one or more of these projects, The proposing entity may file application with the FERC for award of the CWIP and abandonment transmission rate incentives that are typical for projects of this size.

846 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, new Black Oak - Woodside - Goose Creek 500 kV line, New Hunterstown-Doubs-Goose Creek 500 kV line, plus various modifications to existing lines and substations

Proposal permitting and overhead costs are captured on component 10C2.

See attachment 1 for flowgate information.

853 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, New Gant 500 kV substation, New 502 Junction - Black Oak - Woodside - Gant 500 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in Component 4CA.

See attachment 1 for flowgate information.

853 v2 DOM See Proposal for Information See Proposal for Information

New Woodside 500/138 kV substation + SVC + Cap Banks, New Gant 500 kV substation, New 502 Junction - Black Oak - Woodside - Gant 500 kV line, plus various modifications to existing lines and substations.

Proposal permitting and overhead costs are captured in Component 4CA.

See attachment 1 for flowgate information.

856 AEP See Proposal for Information See Proposal for Information

Rebuild the double circuit 138kV line from Leesville station to Str. 17-181 at roughly 5.1 miles. Rebuild the single circuit 138kV line from Str. 17-181 to Altavista station at roughly 3.4 miles. To mitigate outage constraints, the Leesville - Altavista 138kV line will be built in the clear. The Opossum Creek - Smith Mountain 138kV line will be 6 wired from Leesville station to Str. 17-181. To mitigate the overload, the Winter emergency rating needs to be 327 MVA.

858 DOM See Proposal for Information See Proposal for Information

Construct new Greenfield 500kV “Stork” station north of existing Brambleton station. Tap existing Goose Creek–Brambleton 500kV line. Construct 500kV 3-breaker ring bus.

Construct new Greenfield 500/230kV “Flys” station south of existing “Roundtable” station, 230kV double bus double breaker layout. Tap existing Roundtable-Lockridge 230kV. Tap future Roundtable-Barrister 230kV. Rebuild 0.32 mi Roundtable-Flys circuits 1 & 2.

Construct 5.04 miles single circuit underground 500kV line east of new Greenfield 500kV “Stork” 500kV station to the new Greenfield 500/230kV “Flys” station.

Incumbent rebuild 0.69 miles of Roundtable–Buttermilk 230kV. Incumbent rebuild 2.1 miles of Roundtable-Waxpool 230kV. Incumbent rebuild 0.88 miles of Waxpool-Farmwell 230kV. Incumbent upgrade (6) CBs at Roundtable to 5000A.

Incumbent voltage support to address voltage needs in the load area. These supports include an additional (2) 150 MVAr fixed shunt capacitor banks (or one 300 MVAr fixed) at Wishingstar 500 kV. An addition of (2) 150 MVAr fixed shunt capacitor banks (or one 300 MVAr fixed) at Goose Creek 500kV. Adding (1) 150MVAr fixed shunt capacitor bank to existing Cabin Run 230kV station. Adding (2) 150MVAr fixed shunt capacitor banks to existing Pacific 230kV station.

904 AEP/DOM See Proposal for Information See Proposal for Information

Add (2) 765kV breakers at Joshua Falls to create a 2-breaker ring with the transformer still connected off the bus. Remove CT and RTL limits to bring both 765kV lines up to the 3000A wavetrap rating. Construct new “Yeat” 765/500/230kV station near existing Bristers 500/230kV substation. This substation will have (10) 500kV breakers, (2) 765/500kV transformers, (2) 500/230kV transformers, (2) 230kV CB’s and (1) 765kV CB. Construct 135-mile single circuit 765kV greenfield line connecting Joshua Falls 765kV and new Greenfield Yeat 765kV stations. Cut in Bristers–Ox 500kV and Meadowbrook–Vint Hill 500kV lines into Yeat’s 500kV yard. AEP installs a new 12-mile dbl ckt BOLD (Breakthrough Overhead Line Design) 230kV line from Yeat–CloverHIll. Dominion installs a new 7.5-mile dbl ckt BOLD (Breakthrough Overhead Line Design) 230kV line from Warrenton–Wheeler. Dominion installs new 0.1% reactor at Vinthill on Vinthill–Morrisville. Dominion Install new 0.1% reactor at Vinthill on Vinthill–Loudoun 1. Dominion Rebuilds 1.7 miles 230kV line from Marsh Run–RemingtonCt as double circuit. Dominion replaces remote end equipment to bring rating up on 230kV line from Wheeler–Linton Tap–Atlantic. Dominion rebuilds the 0.23-mile line between Bristers 500kV and Yeat 500kV. Dominion installs (2) 230kV breakers at Wheeler substation.

923 DOM See Proposal for Information See Proposal for Information

Construct approximately 40.5-miles of a new 500 kV transmission line from Lexington to Dooms with current 500 kV standards.

948 DOM See Proposal for Information See Proposal for Information

The Muddy Creek portion of PEBO 215 can be energized in 2027 to incrementally resolve PJM reliability need.

New 12-terminal 500/230kV Bartholow substation with 6-terminal 500kV and 6-terminal 230kV, two 500/230kV transformers, two cap banks, and SVC. Interconnected with 500kV Doubs, Conastone, Brighton double circuit, Goram, and interconnected with 230kV Mt. Airy, double circuit Conastone, double circuit Grisham, and Otter Creek. New 230kV double circuit Bartholow to Conastone transmission line, new 230kV double circuit Bartholow to Grisham transmission line, and new 230kV Bartholow to Otter Creek transmission line. New 500kV Bartholow to Goram 500kV transmission line. New 3-terminal 500/230kV Goram substation with one 500/230kV transformer, interconnected with 500kV TMI, Peach Bottom, and Bartholow substations, and interconnected with 230kV Otter Creek substation. New 230kV Goram to Otter Creek transmission line. New 8-terminal 230kV Grisham substation with two cap banks and SVC, interconnected with 230kV Nimbus, Buttermilk, Pacific, BECO, and double circuit Bartholow. New 6-terminal 500/230kV North Delta substation with two 500/230kV transformers, interconnected with 500kV Delta York, Peach Bottom, and Conastone, and interconnected with 230kV Cooper and double circuit Graceton. New 500kV North Delta to Conastone transmission line. New 230kV double circuit North Delta to Graceton transmission lines and new 230kV North Delta to Cooper transmission line. Upgrade limiting elements of lines connecting North Peach Bottom and South Peach Bottom 500kV to achieve required rating. New 230kV double circuit Keeney to Waugh Chapel transmission line.

Proposal permitting and overhead costs are captured in component 26A.

See attachment 1 for flowgate infromation.

951 DOM See Proposal for Information See Proposal for Information

New Pike 500/138 kV substation + SVC + Cap Banks, new Black Oak- Pike - Goose Creek 500 kV line, plus various modifications to existing substations.

Proposal permitting and overhead costs are captured on component 10C2.

See attachment 1 for flowgate information.

962 MAAC/DOM See Proposal for Information See Proposal for Information

500kV Greenfield line from Doubs Station to Peach Bottom Station Circuit #1.
500kV Greenfield line from Doubs Station to Peach Bottom Station Circuit #2.
Reconductor 500kV Line from Doubs Station to Goose Creek Station

967 DOM See Proposal for Information See Proposal for Information

This project serves to wreck/rebuild segment one of 230kV line 2054, demarcation point between Charlottesville Substation to Proffit D.P. using double-circuit capable 500/230 kV poles (the 500kV circuit will not be wired as part of this project). The line will be rebuilt with 3-phase 2-768 ACSS Maumee Type 13 bundled conductor and two (2) DNO-11410 shield wire. Switches and line lead at Charlottesville substation will be upgraded to 4000A.

Upgrading line #2054, causes an overload on lines #233 and #291 under Summer Generator Deliverability study for the loss of line #553. This overload can happen by adding some new loads in Louisa area as well. By wrecking and rebuilding lines #233 and #291 using (2) 768.2 ACSS/TW (20/7) “MAUMEE” conductor with 3948A ampacity, 1573MVA, and upgrading the ratings of substation equipment at Charlottesville, Crozet, Barracks Rd, Hydraulic Rd and Dooms, the overload is mitigated.

977 DOM See Proposal for Information See Proposal for Information

Construct new “Yeat” 500/230kV station near Bristers 500/230kV substation. This substation will have (10) 500kV breakers, (2) 500/230kV transformers, and (2) 230kV CBs. Cut in Bristers–Ox 500kV and Meadowbrook–Vint Hill 500kV lines into Yeat’s 500kV yard. The Proposing Entity installs a new 12-mile dbl ckt BOLD (Breakthrough Overhead Line Design) 230kV line from Yeat–Clover Hill. The Proposing Entity installs a new 7.5-mile dbl ckt BOLD (Breakthrough Overhead Line Design) 230kV line from Warrenton–Wheeler. Dominion to install new 0.1% reactor at Vint Hill on Vint Hill–Morrisville. Dominion to install new 0.1% reactor at Vint Hill on Vint Hill–Loudoun 1. Dominion rebuilds 1.7 miles 230kV line from Marsh Run–Remington Ct as double circuit. Dominion replaces remote end equipment to bring rating up on 230kV line from Wheeler–Linton Tap–Atlantic. Dominion rebuilds the 0.23-mile line between Bristers 500kV and Yeat 500kV. Dominion installs (2) 230kV breakers at Wheeler substation.


Proposal ID Target Zone Analysis Type Flowgate Project Description
473 DOM Thermal, Gen Deliv 2022W2-N1-LLT1, 2022W2-GD-LL1 Re-route one (1) circuit from the Bremo substation to the Fork Union substation, approximately 1.6 miles. All transmission line will be installed within the existing ROW extents via the use of one (1) set of double circuit structures. Line 2193 (230kV) will be rebuilt with the existing line 2111 (230kV).

This proposal provides a direct connect between Bear Garden substation and Fork Union substation by wrecking and rebuilding line #2193 as a double circuit using a conductor with summer rating of 1573MVA and connecting it to line #2111. Fiber optic communication will be considered for this line.

At Fork Union, line leads for line #2193 will be upgraded to 4000A. Also, line #2111 will be terminated into a third row of breaker and a half string with two 4000A breakers and associated switches. This will lead to line #2111 Bear Garden – Fork Union and Line #2193 Bremo – Fork Union. No upgrades at Bear Garden is required. However, controller and relay setting will be updated.
648 DOM Thermal N-1-1 2022W2-N2-WLD1, 2022W2-N2-SLD1, 2022W2-N2-WLD2, 2022W2-N2-SLD2 Cut existing Line #2183 (Brambleton to Poland Road) and extend double circuit 230kV lines creating new Line #2210 (Brambleton to Evergreen Mills) and Line #2183 (Evergreen Mills to Poland Road)
873 DOM Thermal, Gen Deliv 2022W2-N1-LLT1, 2022W2-GD-LL1 This proposal solves the 10% overload on Bremo TX#9 under N-1 contingency in 2027 light load case. It also increases the reliability of the grid by using breaker and a half scheme for transmission equipment connections at Fork Union vs. straight bus configuration at Bremo substation.

It includes relocation of all the six transmission lines and transformers at Bremo substation to Fork Union substation, and addition of a second 224 MVA 230/115 KV transformer at Fork Union.

All transmission lines need to fit in the existing right-of-way using three double-circuit lines. The six transmission lines that need to fit in the existing right-of-way are 230KV lines #298, Line #2111, Line #2106, and Line #2027, 138KV Line #8, and 115KV Line #4.

Proposal ID Target Zone Analysis Type Flowgate Project Description
476 MetEd Gen Deliv 2022W1-GD-S14, 2022W1-GD-W33, 2022W1-GD-S578, 2022W1-GD-W391, 2022W1-GD-W37, 2022W1-GD-S10, 2022W1-GD-S570, 2022W1-GD-W376 Rebuild the Hunterstown – Carroll 115/138 kV Corridor as Double Circuit using 230kV construction standards. New circuit will be operated at 230kV. Existing circuit to remain at 115/138kV. Construct a new 230 kV Ring Bus at Carroll (PE) and add a new 230 kV Breaker to the Hunterstown 230 kV Substation.
236 PECO/DPL Gen Deliv 2022W1-GD-S36 Upgrade dead end structures on Conowingo - Colora line in DPL to increase the line ratings.
21 APS Thermal 2022W1-N2-VD1 through 2022W1-N2-VD198/ 2022W1-SVD1 through 2022W1-N2-SVD41 Install two new 500 kV breakers on the existing open SVC string to create a new bay position. Relocate & Re-terminate facilities as necessary to move the 500 kV SVC into the new bay position. Install a 500 kV breaker on the 500/138 kV #3 transformer. Upgrade relaying at Black Oak Substation.
209 MetEd Gen Deliv 2022W1-GD-S14, 2022W1-GD-W33, 2022W1-GD-S578, 2022W1-GD-W391, 2022W1-GD-W37, 2022W1-GD-S10, 2022W1-GD-S570, 2022W1-GD-W376 Rebuild/Reconductor the Germantown - Lincoln 115 kV Line. Approximately 7.6 miles. Upgrade limiting terminal equipment at Lincoln, Germantown and Straban.
94 BGE Gen Deliv 2022W1-GD-W42, 2022W1-GD-S38 Reconductor two (2) 230 kV circuits from Conastone to Northwest #2.
633 APS Gen Deliv 2022W1-GD-S14, 2022W1-GD-W53, 2022W1-GD-S38, 2022W1-GD-W33, 2022W1-GD-W55, 2022W1-GD-W36, 2022W1-GD-W391, 2022W1-GD-W35, 2022W1-GD-W57, 2022W1-GD-S10, 2022W1-GD-W411, 2022W1-GD-S651, 2022W1-GD-S578, 2022W1-GD-S634, 2022W1-GD-S570, 2022W1-GD-W376, 2022W1-GD-S1043, 2022W1-GD-W42, 2022W1-GD-S29, 2022W1-GD-S558, 2022W1-GD-S559, 2022W1-GD-W60, 2022W1-GD-W623, 2022W1-GD-W37, 2022W1-GD-W39, 2022W1-GD-W388, 2022W1-GD-W387 This Proposed Solution is a resubmittal of the modified Independence Energy Connection (IEC) Project. The Proposed Solution consists of: (1) the IEC West Portion, which is comprised of approximately 29 miles of new double-circuit 230 kV AC overhead transmission line between the existing Potomac Edison Ringgold Substation in Washington County, Maryland to a new Rice Substation in Franklin County, Pennsylvania; and (2) the reconfigured IEC East Portion, which is primarily comprised of adding 230 kV AC overhead transmission lines between a new Furnace Run Substation in York County, Pennsylvania, and the existing BGE Conastone (via Baltimore County) and Graceton Substations in Harford County, Maryland.
880 MetEd Gen Deliv 2022W1-GD-S29, 2022W1-GD-W36, 2022W1-GD-S634 Install second 500/230kV Transformer with additional 500 and 230 bus expansions.
912 PPL/BGE Gen Deliv 2022W1-GD-S1043, 2022W1-GD-W411, 2022W1-GD-W623, 2022W1-GD-W55 Rebuild 1.4 miles of existing single circuit 230 kV tower line between BGE's Graceton substation to the PPL tie-line at the MD/PA state line to double circuit steel pole line with one (1) circuit installed to uprate 2303 circuit.
994 AEP/DEOK Gen Deliv 2022W1-GD-S586, 2022W1-GD-W377 Build a new 138 kV 3-breaker ring station called “Johnson Fork” just North of the existing Wesley SW 138 kV station (AEP). Bring the existing Tanners Creek–College Corner 138 kV line (AEP) “in and out” of Johnson Fork. Build a new 138 kV line from Johnson Fork (AEP) to Willey (Duke) stations (13 miles). Install 2 breakers at Willey to terminate the new line.
446 AEP/DEOK Gen Deliv 2022W1-GD-S586, 2022W1-GD-W377 Build a new 138 kV 4-breaker ring station called “Pribble." Bring the existing Tanners Creek–College Corner (AEP) & Miami Fort–Hubbell (Duke) 138 kV lines “in and out” of Pribble station. Rebuild Tanners Creek–Pribble 138 kV (5 miles) and upgrade station equipment at Tanners Creek 138 kV. Rebuild Pribble-Miami Fort 138 kV (6 miles).
893 AEP/DEOK Gen Deliv 2022W1-GD-S586, 2022W1-GD-W377 Build a new 345 kV line from Tanners Creek station (AEP) to Miami Fort (Duke) station (11.4 miles). Rebuild a portion of the existing Tanners Creek – Hanna 345 kV and Greendale – Miami Fort 138 kV lines to double circuit (4 & 3 miles respectively) to facilitate construction of the new line. Install 1 breaker at Tanners Creek and 2 breakers at Miami Fort to terminate the new line.
965 AEP/OVEC Gen Deliv 2022W1-GD-S632 Replace four Clifty Creek 345 kV 3000 A switches with 5000 A 345 kV switches. Anticipated SN/SE rating for the branch section to be addressed (242865 to 248000) by the project is 2354/2354 MVA.
289 AEP Thermal 2022W1-N1-LLVM2, 2022W1-N1-LLVM1, 2022W1-N1-LLVD1, 2022W1-N1-LLVD2 At West Bellaire 345kV, the M1 breaker will be moved to the N breaker string, becoming N1. The Tidd circuit will connect to the N string, between N1 and N. Jumpers/conductor will be installed in the place of old breaker M1, to complete the M string. Station protection and SCADA updates will be completed. The Tidd 345kV T-Line will need shifted slightly, to connect to the new station bay to the east.
27 AEP/DEOK Gen Deliv 2022W1-GD-S586, 2022W1-GD-W377 Install at Tanners Creek a 345 kV 5000 A 63 kA circuit breaker "R" and move the Tanners Creek - East Bend 345 kV circuit from the "T" and "T1" line position to the "R and "R1" line position, thus mitigating the College Corner - Collinsville 138 kV overload by eliminating the contingency causing the issue.
127 PPL Gen Deliv 2022W1-GD-S595 Reterminate the Lackawanna T3 and T4 500 / 230 kV transformers on the 230 kV side to remove them from the 230 kV buses and bring them into dedicated bay positions that are not adjacent to one another.
553 PPL Gen Deliv 2022W1-GD-S596 Replace the existing Lackawanna 500/230 kV T3 and T4 transformers with larger 1250 MVA units. Upgrade bay equipment to accommodate the new higher rated transformers.
907 PPL Gen Deliv 2022W1-GD-S597 Install a new 1500 MVA 500/230 kV transformer at Lackawanna substation. Tie into bay #1 in the Lackawanna 500 kV yard. Install four single phase transformer units (one on-site spare). Install bus work necessary to facilitate restoration with the onsite spare. Install MODs on the high and low-side of the 500/230 kV transformer. Install a 230 kV dead-end for termination of the Lackawanna Energy 230kV lead line. The 500/230 kV transformer will have double-bundle 1590 ACSR leads on the high-side. Re-terminate the Lackawanna - Lackawanna Energy 230kV line into the dead-end for the new 500/230 kV transformer at Lackawanna utilizing triple bundle 1590 45/7 ACSR conductor and dual 144 OPGW.

Proposal ID Target Zone Analysis Type Flowgate Project Description
40 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Swap 345kV transmission line at Green Acres, rebuild University Park to Olive 345kV lines and add a reactor along Crete- St John 345kV line.
82 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Add a new 345 kV double circuit to tap existing lines and connect to an existing sub, and reconfigure existing lines at the sub.
91 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Goodenow-Lemon Lake 345kV Greenfield Line and Stations (Enhanced).
165 AEP/NIPSCO Summer Gen Deliv MDW1-GDS1620 Dumont-Stillwell Sag Study
401 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Add a new 345kV double circuit to reconfigure existing lines.
541 AEP/NIPSCO Winter Gen Deli MDW1-GD-W392-MDW1-GD-W393 Peregrine Ditch
597 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Goodenow-Lemon Lake 345kV Greenfield Line and Stations (Robust).
612 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Goodenow-Lemon Lake 345kV Greenfield Line and Stations (Basic).
644 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Swap 345kV transmission line at Green Acres, rebuild University Park to Olive 345kV lines.
664 ComEd Winter Gen Deliv, Summer Gen Deliv, Market Efficiency MDW1-GD-S1620,MDW1-ME-01,MDW1-ME-02,MDW1-GD-W392,MDW1-GD-W393,MDW1-GD-W309,MDW1-GD-W404,MDW1-GD-W419,MDW1-ME-04,MDW1-GD-W172,MDW1-GD-W171,MDW1-GD-W188,MDW1-GD-W190,MDW1-GD-W185,MDW1-GD-W332,MDW1-GD-W331,MDW1-ME-03 Add a new 345 kV double circuit line looping the existing line into a new substation.
908 AEP/ComEd Winter Gen Deliv MDW1-GD-W392-MDW1-GD-W393 Olive-University Park Sag Study

Proposal ID Target Zone Analysis Type Flowgate Project Description
176 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6 Reconductor 345kV E. Frankfort to Crete to St John transmission line
805 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6 Cedar Run 345kV Transmission Project
253 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6, GD-W2-259,GD-W2-258 Rebuild 345 kV Lines 6607/6608 East Frankfort - Crete and 94507/97008 Crete - St. John
994 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6, GD-W2-259,GD-W2-258 Install Series Inductor on Line 94507 Crete - St. John
408 ComEd Winter Gen Deliv GD-W2-W211, GD-W2-W214, GD-W2-51 Install 345 kV Bus Tie Circuit Breaker at Dresden Station
442 ComEd Winter Gen Deliv GD-W2-W211, GD-W2-W214 East Spring 345kV Transmission Project
977 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6, GD-W2-259,GD-W2-258 Rebuild 345 kV double circuit Lines 94507 and 97008 Crete - Indiana
727 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6 Swap 345kV transmission line at Green Acres and reconductor Crete to St John 345kV line
117 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6 Series reactor along Crete-St John 345 kV line and reconductor Crete to St John 345kV line
335 ComEd Winter Gen Deliv GD-W2-W5, GD-W2-W6 Loop-in Bloom –Davis 345kV line at New NEET proposed Illinois Substation + Loop-in NEET owned Crete- St John 345 kV line at new NEET proposed State Line 345 kV sub

Proposal ID Redacted BPU Form Target Zone(s) Analysis Type Flowgate Project Description
11 11 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Add 1x500/230 kV Transformer ID 1 at NEETMA proposed Wheeler substation in series with new proposed Wheeler- Gracestone 230kV OH line circuit 1.
15 15 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Two 1,500 MW HVDC Symmetrical Monopole systems connecting offshore platforms in the Hudson South lease area to a new Neptune 230 kV switchyard near the existing Oceanview 230 kV substation.
17 17 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Project proposal to build the necessary transmission to meet New Jersey’s goal of facilitating the delivery of a total of 7,500 MW of offshore wind by 2035.
21 21 NJ OSW Generation Deliverability Summer/Winter See Proposal Document A 91MW/ 364MWh Battery Energy Storage System (BESS) on property adjacent to Werner substation. The proposed BESS facility will be interconnected at 230kV.
27 27 NJ OSW Generation Deliverability Summer/Winter See Proposal Document One 1,500 MW HVDC Symmetrical Monopole system connecting offshore platforms in the Hudson South lease area to a new Neptune 230 kV switchyard near the existing Oceanview 230 kV substation.
44 44 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrades for 2-D30 injection (PJM Proposal ID 461)
63 63 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Build a new station called “North Delta” with two 500/230 kV 1500 MVA transformers and 9 breakers (4 high side and 5 low side breakers in ring bus configuration). Bring two existing lines, Peach Bottom – Delta Power Plant 500 kV and Cooper - Graceton 230 kV, “in and out” of North Delta. Build a new North Delta – Graceton 230 kV line by rebuilding 6.07 miles of the existing Cooper - Graceton 230 kV line to double circuit. Install 1 breaker at Graceton 230 kV to terminate the new line from North Delta.
72 72 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Clean Energy Gateway - Offshore consists of two (2) 345kV offshore substations and eight (8) 345kV submarine cables that connect to the Proposal Option 1b.
103 103 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Old York Transmission Project includes a new 500/230kV substation. The 500kV yard will include a 4 position breaker and a half configuration 500kV gas insulated substation (GIS).
127 127 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrade Cardiff-Lewis #2, Lewis #1-Lewis #2, Cardiff-New Freedom, Peach Bottom-Conastone, Richmond-Waneeta, Peach Bottom-Furnace Run circuits, rebuild Cardiff substation and rebuild Cardiff-New Freedom line.
131 131 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 1,400 MW offshore transmission link connecting the Atlantic Shores 3 (“AS3”) offshore wind lease area to the 230 kV Sewaren substation located in Woodbridge Township, Middlesex County, New Jersey. This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.12.
137 137 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the offshore substation platforms (OSP) at Atlantic Shores 2 ("AS2") and Atlantic Shores 1 ("AS1") offshore wind farms. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.7.
145 145 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,148 MW offshore transmission link connecting the Orsted's Ocean Wind 2 (“OW2”) offshore wind farm (awarded as part of second offshore wind solicitation) to the 500 kV Deans substation located in South Brunswick, New Jersey (identified as one of the default Point of Interconnections by PJM Interconnection). This 1,148 MW, 400 kV offshore transmission link project is referred to as Boardwalk Power Option 2.8.
158 158 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Provides reinforcements to allow delivery of greater than 8300MW of injections associated with Proposals 11, 15, 27, 44, 250, 298, 315, 331, 359, 461, 520, 587, 604, 651, 793, 860, 878, 982.
171 171 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This proposal facilitates an additional injection of 800MW of energy and capacity from one or more Offshore Wind Projects construction to the 230kV system located at Werner Substation through such upgrades to Werner Substation, as may be required. This Additional Offer is contingent upon the selection of either Base Offer 1 (Proposal 582)or Base Offer 2 (Proposal 490).
172 172 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Second 1200MW Injection (must be combined with Proposal No. 210).
180 180 NJ OSW Generation Deliverability Summer/Winter See Proposal Document 1) Brunswick to Deans Subproject, 2) Linden Inside Plant Subproject, 3) Windsor to Clarksville Subproject, 4) Deans Inside Plant Subproject, 5) Bergen Inside Plant Subproject.
183 183 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,400 MW offshore transmission link connecting the Atlantic Shores 3 (“AS3”) offshore wind lease area to the 230 kV Sewaren substation located in Woodbridge Township, Middlesex County, New Jersey. This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.
203 203 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Broad Creek - Robinson Run Transmission Project.
208 208 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Sewaren/Larrabee 400kV Collector is an offshore transmission solution designed to deliver up to 2800 MW of clean, reliable OSW energy to the State of New Jersey. The Project is comprised of two (2) HVDC systems.
210 210 NJ OSW Generation Deliverability Summer/Winter See Proposal Document First 1200MW Injection (may be combined with Proposal No. 172 and 769)
214 214 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Sewaren 400kV Collector is an offshore transmission solution designed to deliver up to 1400 MW.
229 229 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Silver Run Upgrade project includes adding a third set of submarine cables, rerating the overhead segment, and upgrading terminal equipment to achieve a higher rating for the Silver Run - Hope Creek 230kV Transmission Line.
230 230 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Larrabee 400kV Collector is an offshore transmission solution designed to deliver up to 1400 MW.
243 243 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the new offshore substation platforms (OSP) at Atlantic Shores 2 ("AS2") offshore Wind Energy Area and Ocean Wind 2 ("OW2") offshore wind farm. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.5.
248 248 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the offshore substation platforms (OSP) at Ocean Wind 2 ("OW2") and Atlantic Shores 1 ("AS1") offshore wind farms. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.6.
250 250 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Four 1,500 MW HVDC Symmetrical Monopole systems connecting offshore platforms in the Hudson South lease area to a new Fresh Ponds 500 kV substation near the existing Deans 500 kV switchyard.
285 285 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 1,400 MW offshore transmission link connecting the Atlantic Shores 2 (“AS2”) offshore wind lease area to the 230 kV Larrabee substation located in Howell Township in Monmouth County, New Jersey. This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.7.
294 294 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Clean Energy Gateway - Offshore consists of two (2) 345kV offshore substations and eight (8) 345kV submarine cables that connect to the Proposal Option 1b.
296 296 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Build a new station called “North Delta” with one 500/230 kV 1500 MVA transformer and 6 breakers (3 high side and 3 low side breakers).
298 298 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Two 1,200 MW HVDC Symmetrical Monopole systems connecting offshore platforms in the Hudson South lease area to a new Neptune 230 kV switchyard near the existing Oceanview 230 kV substation.
315 315 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrades for 2-D45 injection (Proposal No. 860).
321 321 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Mid-Atlantic Offshore Development (MAOD)'s Option 2 Proposal 3 is a cost effective and highly reliable solution to deliver 4,800 MW of offshore energy from offshore wind turbines in various BOEM lease areas to New Jersey on the PJM bulk electrical grid, centered around 4 HVDC links.
330 330 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Reconductor the 0.33 mile PPL EU portion of the Springfield - Gilbert 230 kV line with 1590 ACSS 54/19 conductor to achieve a new rating of SN/SE: 830/954 MVA and WN/WE: 939/1087 MVA.
331 331 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrades for Oceanview 3000 MW Injection.
345 345 NJ OSW Generation Deliverability Summer/Winter See Proposal Document New 17.23 mile 500 kV line from Peach Bottom station (PECO) to Conastone station (BG&E).
359 359 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Offshore 230 kV AC offshore platform interconnection. Linked to Proposals 11, 15, 27, 44, 250, 298, 315, 331, 359, 461, 520, 587, 604, 651, 793, 860, 878, 982.
376 376 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This proposal facilitates an additional injection of 400MW of energy and capacity from one or more offshore wind projects construction to the 230kV system located at Werner Substation through such upgrades to Werner Substation, as may be required. This Additional Offer is contingent upon the selection of either Base Offer 1 (Proposal 582)or Base Offer 2 (Proposal 490).
397 397 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Sewaren 320kV Collector is an offshore transmission solution designed to deliver up to 1200 MW of clean, reliable OSW energy to the State of New Jersey.
419 419 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Build a 2.3 mile 230 kV line from Claymont Station (DPL&E) to Bridgeport Station (ACE) using three 3-core submarine cables.
428 428 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the new offshore substation platforms (OSP) at Hudson South 1 ("HS1") and Hudson South 2 ("HS2") associated with the Hudson South Wind Energy Area A and E, respectively, in the Hudson South Call Area. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.1.
431 431 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Mid-Atlantic Offshore Development (MAOD)'s Option 2 Proposal 1 is a cost effective and highly reliable solution to deliver 2,400 MW of offshore energy from offshore wind turbines in various BOEM lease areas to New Jersey on the PJM bulk electrical grid, centered around 2 HVDC links.
453 453 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Project proposal to build the necessary transmission to meet New Jersey’s goal of facilitating the delivery of a total of 7,500 MW of offshore wind by 2035.
461 461 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Two 1,500 MW HVDC Symmetrical Monopole systems connecting offshore platforms in the Hudson South lease area to a new Fresh Ponds 500 kV substation near the existing Deans 500 kV switchyard.
490 490 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This proposal facilitates the injection of 2400MW of energy and capacity from one or more Interconnecting Offshore Wind Projects through the construction of onshore facilities to deliver energy to the Deans Switching Station 500kV transmission network.
520 520 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Required upgrades to facilitate 2-O15 injection (Proposal No. 27).
551 551 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Mid-Atlantic Offshore Development (MAOD)'s Option 2 Proposal 2 is a cost effective and highly reliable solution to deliver 3,600 MW of offshore energy from offshore wind turbines in various BOEM lease areas to New Jersey on the PJM bulk electrical grid, centered around 3 HVDC links.
568 568 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,510 MW offshore transmission link connecting the Atlantic Shores 1 (“AS1”) offshore wind lease area to the 500 kV Deans substation located in South Brunswick, New Jersey (identified as one of the default Point of Interconnections by PJM Interconnection). This 1,510 MW offshore transmission link project is referred to as Boardwalk Power Option 2.10.
574 574 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,400 MW offshore transmission link connecting the Atlantic Shores 3 ("AS3") offshore wind lease area to the 500 kV Deans substation located in South Brunswick, New Jersey (identified as one of the default Point of Interconnections by PJM Interconnection). This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.3.
582 582 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This proposal facilitates the injection of 1200MW of energy and capacity from one or more Interconnecting Offshore Wind Projects through the construction of onshore facilities to deliver energy to the Deans Switching Station 500kV transmission network.
587 587 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Wiley Rd – Conastone 500 kV Project using adjacent ROW.
594 594 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Clean Energy Gateway - Offshore consists of two (2) 345kV offshore substations and eight (8) 345kV submarine cables that connect to the Proposal Option 1b.
604 604 NJ OSW Generation Deliverability Summer/Winter See Proposal Document One 1,200 MW HVDC Symmetrical Monopole system and one 1510 MW HVDC Symmetrical Monopole system connecting offshore platforms to deliver the Atlantic Shores and Ocean Wind 2 offshore wind projects to a new Reega 230 kV switchyard. Loop in the existing New Freedom to Cardiff 230 kV line into Reega 230 kV.
613 613 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Larrabee 320kV Collector is an offshore transmission solution designed to deliver up to 1200 MW of clean, reliable OSW energy to the State of New Jersey.
627 627 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Clean Energy Gateway - Offshore consists of two (2) 345kV offshore substations and eight (8) 345kV submarine cables that connect to the Proposal Option 1b.
629 629 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Clean Energy Gateway - Offshore consists of two (2) 345kV offshore substations and eight (8) 345kV submarine cables that connect to the Proposal Option 1b.
651 651 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrades for Deans 6000 MW Injection.
683 683 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Sewaren/Deans/Larrabee 400kV Collector is an offshore transmission solution designed to deliver up to 4200 MW of clean, reliable OSW energy to the State of New Jersey.
734 734 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrade Cardiff-Lewis #2, Lewis #1-Lewis #2, Cardiff-New Freedom, Peach Bottom-Conastone, Richmond-Waneeta, Peach Bottom-Furnace Run circuits, rebuild Cardiff substation and rebuild Cardiff-New Freedom line to add a second circuit
748 748 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the new offshore substation platforms (OSP) at Hudson South 2 ("HS2") and Atlantic Shores 2 ("AS2") offshore Wind Energy Areas. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.
769 769 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Third 1200MW Injection (musty be combined with Proposal No. 172 and 210).
781 781 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Clean Energy Gateway - Offshore consists of two (2) 345kV offshore substations and eight (8) 345kV submarine cables that connect to the Proposal Option 1b.
793 793 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrades for 2-C27 injection (Proposal 793).
797 797 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Build new transition vault connecting 275 kV off shore cables and 275 kV on shore cables, build new 275 kV transmission lines between transition vault and new 275-230 kV substation near Cardiff, and build new 275-230 kV substation near Cardiff connected to existing substation at Cardiff
802 802 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,400 MW offshore transmission link connecting the Hudson South 2 (“HS2”) offshore wind lease area (Wind Energy Area E in Hudson South Call Area) to the 230 kV Sewaren substation located in Woodbridge Township, Middlesex County, New Jersey. This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.
831 831 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,400 MW offshore transmission link connecting the Hudson South 2 (“HS2”) offshore wind lease area (Wind Energy Area E in Hudson South Call Area) to the 500 kV Deans substation located in South Brunswick, New Jersey (identified as one of the default Point of Interconnections by PJM Interconnection). This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.2.
841 841 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,400 MW offshore transmission link connecting the Hudson South 1 (“HS1”) offshore wind lease area (Wind Energy Area A in Hudson South Call Area) to the 500 kV Deans substation located in South Brunswick, New Jersey (identified as one of the default Point of Interconnections by PJM Interconnection). This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.1
860 860 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Three 1,500 MW HVDC Symmetrical Monopole systems connecting offshore platforms in the Hudson South lease area to a new Fresh Ponds 500 kV substation near the existing Deans 500 kV switchyard.
871 871 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The Sewaren/Deans 400kV Collector is an offshore transmission solution designed to deliver up to 2800 MW of clean, reliable OSW energy to the State of New Jersey.
878 878 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Required upgrades to facilitate 2-O24 injection (Proposal 298).
882 882 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,148 MW offshore transmission link connecting the Orsted's Ocean Wind 2 (“OW2”) offshore wind farm (awarded as part of second New Jersy offshore wind solicitation) to the 500 kV Deans substation located in South Brunswick, New Jersey (identified as one of the default Point of Interconnections by PJM Interconnection). This 1,148 MW, 320 kV offshore transmission link project is referred to as Boardwalk Power Option 2.9.
889 889 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the new offshore substation platforms (OSP) at Hudson South 1 ("HS1") and Atlantic Shores 3 ("AS3") Wind Energy Areas. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.2.
894 894 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Install a third submarine 230kV conductor underneath the Delaware River and connect to the existing OH lines at both sides of the river.
896 896 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 700 MW offshore transmission link between the new offshore substation platforms (OSP) at Atlantic Shores 2 ("AS2") and Atlantic Shores 3 ("AS3") offshore Wind Energy Areas. This 700 MW offshore transmission link is referred to as Boardwalk Power Option 3.4.
921 921 NJ OSW Generation Deliverability Summer/Winter See Proposal Document The project proposes a 1,200 MW offshore transmission link connecting the Atlantic Shores 2 (“AS2”) offshore wind lease area to the 230 kV Larrabee substation located in Howell Township in Monmouth County, New Jersey. This 1,200 MW offshore transmission link project is referred to as Boardwalk Power Option 2.6.
929 929 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrade Cardiff-Lewis #2, Lewis #1-Lewis #2, Cardiff-New Freedom, Peach Bottom-Conastone, Richmond-Waneeta, Peach Bottom-Furnace Run circuits, rebuild Cardiff substation, expand Orchard substation and build new 230 kV line from Cardiff to Orchard.
944 944 NJ OSW Generation Deliverability Summer/Winter See Proposal Document This project proposes a 1,400 MW offshore transmission link connecting the Hudson South 2 (“HS2”) offshore wind lease area (Wind Energy Area E in Hudson South Call Area) to the 230 kV Sewaren substation located in Woodbridge Township, Middlesex County, New Jersey. This 1,400 MW offshore transmission link project is referred to as Boardwalk Power Option 2.
975 975 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Upgrade Cardiff-Lewis #2, Lewis #1-Lewis #2, Cardiff-New Freedom, Peach Bottom-Conastone, Richmond-Waneeta, Peach Bottom-Furnace Run circuits and rebuild Cardiff substation.
982 982 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Wiley Rd – Wheeler 500 kV Project using adjacent ROW, Hope Creek PARs.
990 990 NJ OSW Generation Deliverability Summer/Winter See Proposal Document Clean Link New Jersey is proposing a modular HVDC Power Corridor development to support the reliable and cost-effective delivery of the Offshore Wind resources to New Jersey consumers. Clean Link New Jersey’s technical solution responds to Option 2 within PJM’s proposal window, by providing new offshore transmission facilities to default Points of Interconnection (“POI”) on the PJM operated grid within New Jersey.

Proposal ID Target Zone(s) Analysis Type Congestion Driver Major Component/Project Description
102 APS Market Efficiency ME-3 Capacitor bank at Reston 230 kV substation
425 APS Market Efficiency ME-3 Replace terminal equipment on the French’s Mill-Junction 138 kV line. Reconductor Messick Road-Ridgeley 138 kV line.
540 APS Market Efficiency ME-3 Capacitor bank at Bull Run 230 kV substation
547 APS Market Efficiency ME-3 Build 500 kV transmission line connecting Black Oak Substation and Bismark Substation.
756 APS Market Efficiency ME-3 Replace terminal equipment on the French’s Mill-Junction 138 kV line.
196 DOM Market Efficiency ME-5 Charlottesville-Proffit 230kV Line Rebuild.
238 DOM Market Efficiency ME-5 Charlottesville-Gordonsville 230kV Greenfield Line.
309 DOM Market Efficiency ME-5 5 MW Battery Energy Storage System at Louisa CT substation.
327 DOM Market Efficiency ME-5 New Hollymeade Tap 230kV Substation. Charlottesville-Hollymeade Tap-Cash’s Corner-Gordonsville 230kV Line Rebuild.
533 DOM Market Efficiency ME-5 10 MW Battery Energy Storage System at Hollymeade substation.
578 DOM Market Efficiency ME-5 New Hollymeade Tap 230kV Substation.
589 DOM Market Efficiency ME-5 Build Second Charlottesville-Gordonsville 230kV Line. Hollymeade-Cash’s Corner-Gordonsville 230kV Line Rebuild.
632 DOM Market Efficiency ME-5 5 MW Battery Energy Storage System at Gordonsville substation.
651 DOM Market Efficiency ME-5 Charlottesville-Proffit 230kV Line Series Reactor.
669 DOM Market Efficiency ME-5 5 MW Battery Energy Storage System at Hollymeade substation.
692 DOM Market Efficiency ME-5 Sleepy Hollow-Stoney Point 230kV Greenfield Project.
813 DOM Market Efficiency ME-5 New Cismont 230kV Substation. Charlottesville-Hollymeade Tap-Cash’s Corner-Gordonsville 230kV Line Rebuild.
227 PECO Market Efficiency ME-6 Interconnect the Peach Bottom - Limerick 500kV and Cochranville - Newlinville 230kV lines via a new Old Limestone 500/230 kV substation. Build new 230 kV Doe Run substation and interconnect Daleville - Bradford and Clay Tap - Bradford 230kV lines. Construct a new 230 kV line from Old Limestone to Doe Run.
399 PECO Market Efficiency ME-6 Install Smart Wires device in series with the 220-13 and 220-14 Whitpain-Plymouth 230 kV lines and upgrade terminal equipment at Whitpain and Plymouth substations.
704 PECO Market Efficiency ME-6 Upgrade terminal equipment at Whitpain and Plymouth substations.
735 PECO Market Efficiency ME-6 Reconductor the 220-13 and 220-14 Whitpain-Plymouth 230 kV lines.
102 PPL Market Efficiency ME-7 Capacitor bank at Reston 230 kV substation
218 PPL Market Efficiency ME-7 Reconductor the Juniata - Cumberland 230 kV line.
251 PPL Market Efficiency ME-7 Rebuild the existing single circuit Juniata - Cumberland 230 kV section to double circuit. Upgrade the Cumberland to Wil. Grove 230 kV line.
540 PPL Market Efficiency ME-7 Capacitor bank at Bull Run 230 kV substation
738 PPL Market Efficiency ME-7 Build new 500/230 kV Bow Creek tap substation on the Juniata – Alburtis 500kV line. Interconnect North Hershey - Hummelstown and North Lebanon – Copperstone 230kV lines to the Bow Creek substation.

Proposal ID Target Zone(s) Analysis Type Flowgate Comments
445 DOMINION GenDeliv, Thermal GD-S12, GD-S17, GD-S715, GD-S37, GD-S717, N1-ST49 Line #2114 - Reconductor Remington CT to Gainesville - Full
333 DOMINION GenDeliv, Thermal GD-S12, GD-S17, GD-S715, GD-S37, GD-S717, N1-ST49 Line #2114 - Reconductor Remington CT to Gainesville - Full and Upgrade Terminal Equipment at Remington CT and Gainesville
600 DOMINION Thermal N1-ST33 Line 2008 Uprate - Cub Run to Walney
414 DOMINION GenDeliv GD-S19 Line #2141 Lakeview to Carolina 230 kV Rebuild
637 DOMINION Thermal DOM-T3, DOM-T4 Occoquan 500-230kV Transformer (OX Transformer Overload)
319 DOMINION Thermal DOM-T3, DOM-T4 Ox 500-230kV Two(2) Transformer Replacements
292 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Dogwood Run 115/230kV Transmission Project
582 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Dogwood Sprint 115/500kV Transmission Project
57 DOMINION Thermal DOM-T3, DOM-T4 Possum Point 2nd 500-230kV Transformers
561 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Williams Grove - Allen 115 kV line upgrade sourced from Williams Grove 69 kV bus (PPL-Allen Switchyard)
992 MetED Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Williams Grove - Allen 115 kV line upgrade sourced from Williams Grove 230 kV bus (PPL-Allen Switchyard)
386 MetED Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Multi-Driver Project: Allen-Williams Grove Greenfield Line & Reconductor
113 MetED Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Allen-Williams Grove Greenfield Line
298 DOMINION GenDeliv GD-S12, GD-S17, GD-S30, GD-S715, GD-S37, GD-S717 Greenfield Lee District Station
503 AEP Thermal AEP -T15, AEP-T16, AEP -T18, AEP -T19, AEP -T20, AEP -T22, AEP -T23, AEP -T25, AEP-T26, AEP -T27, AEP -T47, AEP -T49, AEP -T51, AEP -T52, AEP -T53, AEP -T54, AEP -T55, AEP -T57, AEP -T73, AEP -T75 LS Rockford - LS West Van Wert 69kV Transmission Project
789 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 New Allen 115 kV Source
560 APS Voltage Drop APS-VD45, APS-VD46 Persia - Elimsport 230kV Transmission Project
608 APS Voltage Drop APS-VD45, APS-VD46 Persia - Yeagertown 230kV Transmission Project
88 PECO/PSG GenDeliv GD-S485, GD-S674, GD-S486 Replace a portion of Croydon-Burlington line conductor
779 APS Voltage Drop APS-VD45, APS-VD46 Shingletown 230 kV Substation: Create a 230 kV Ring Bus
919 APS Voltage Drop APS-VD45, APS-VD46 Shingletown 230 kV: Upgrade #82 Transformer Circuit
477 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD1, N2-SVD2, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Northern Loop STATCOM
823 PENELEC GenDeliv GD-S14, GD-S15, GD-S38 East Towanda - Canyon 230 kV
589 PENELEC GenDeliv GD-S13 East Towanda - North Meshoppen 115 kV
634 PENELEC Voltage Drop, Voltage Magnitude N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N1-SVM1, N1-SVM2, N1-WVM1, N1-WVM2, N1-WVM3, N1-WVM4, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVM7, N2-WVM8 Grover 230 kV Substation: Install dual reactors and convert the station to a ring bus
745 PENELEC Voltage Drop, Voltage Magnitude N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N1-SVM1, N1-SVM2, N1-WVM1, N1-WVM2, N1-WVM3, N1-WVM4, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVM7, N2-WVM8 Marshall 230 kV Substation: Install dual reactors and expand existing ring bus
101 APS/PENELEC Voltage Drop, Voltage Magnitude N2-SVM48, N2-SVM49, N2-SVM50, N2-SVD19, N2-SVD20, N2-SVD21, N2-SVD22, N2-SVD23, N2-SVD24, N2-SVD25, N2-SVD26, N2-SVD27, N2-SVD28, N2-SVD29 Pierce Brook Substation: Install second 230/115 kV transformer
549 ATSI GenDeliv GD-S712 Hayes 2nd Transformer Addition
124 DOMINION End of Life Criteria DOM-O2 Line #557 Elmont – Chickahominy 500 kV Line Rebuild
722 DOMINION Voltage Drop, Voltage Magnitude N1-LLVM1, N1-LLVM2, N1-LLVM3, N1-LLVM4, N1-LLVM5, N1-LLVM6, N1-LLVM7, N1-LLVM8, N1-LLVD1, N1-LLVD2, N1-LLVD3 Install an Approx. 294 MVar Cap Bank at Lexington substation
498 PENELEC Voltage Drop, Voltage Magnitude N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N1-SVM1, N1-SVM2, N1-WVM1, N1-WVM2, N1-WVM3, N1-WVM4, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVM7, N2-WVM8 Grover Substation: Install two reactors and install line breakers
25 AEP Thermal AEP -T43, AEP-T44, AEP-T45, AEP-T46 Albion-Kendallville Rebuild
116 AEP Thermal AEP -T9, AEP -T10, AEP -T11, AEP -T12, AEP -T13, AEP -T14 Bancroft-Milton Rebuild
336 AEP Thermal AEP -T43, AEP-T44, AEP-T45, AEP-T46 Cabell Station Expansion and Cut In
115 AEP Thermal AEP -T39, AEP -T40, AEP -T41, AEP -T42 Salt Fork-Leatherwood Rebuild
920 AEP Thermal AEP -T43, AEP-T44, AEP-T45, AEP-T46 West Cambridge Transformer Addition
202 AEP Thermal AEP -T15, AEP -T16, AEP -T17, AEP -T18, AEP -T19, AEP -T20, AEP -T21, AEP -T22, AEP -T23, AEP -T24, AEP -T25, AEP -T26, AEP -T27, AEP -T28, AEP -T47, AEP -T48, AEP -T49, AEP -T50, AEP -T51, AEP -T52, AEP -T53, AEP -T54, AEP -T55, AEP -T56, AEP -T57, AEP -T58, AEP -T73, AEP -T74, AEP -T75, AEP -T76 Delphos Area Line Rebuilds
786 AEP Thermal AEP -T43, AEP-T44, AEP-T45, AEP-T46 Haviland Sectionalizing Addition
365 AEP Voltage Drop, Voltage Magnitude AEP -T6, AEP -T7, AEP -T8, AEP-VM1, AEP-VM2, AEP-VM3, AEP-VM4, AEP-VM5, AEP-VM6, AEP-VM7, AEP-VM8, AEP-VM9, AEP-VD1, AEP-VD2, AEP-VD3, AEP-VD4, AEP-VD5, AEP-VD6, AEP-VD7, AEP-VD8, AEP-VD9 Accoville-Becco 69 kV
310 AEP Voltage Drop, Voltage Magnitude AEP -T6, AEP -T7, AEP -T8, AEP-VM1, AEP-VM2, AEP-VM3, AEP-VM4, AEP-VM5, AEP-VM6, AEP-VM7, AEP-VM8, AEP-VM9, AEP-VD1, AEP-VD2, AEP-VD3, AEP-VD4, AEP-VD5, AEP-VD6, AEP-VD7, AEP-VD8, AEP-VD9 Becco-Pine Gap Rebuild
488 AEP Voltage Drop, Voltage Magnitude AEP -T6, AEP -T7, AEP -T8, AEP-VM1, AEP-VM2, AEP-VM3, AEP-VM4, AEP-VM5, AEP-VM6, AEP-VM7, AEP-VM8, AEP-VM9, AEP-VD1, AEP-VD2, AEP-VD3, AEP-VD4, AEP-VD5, AEP-VD6, AEP-VD7, AEP-VD8, AEP-VD9 Dehue Expansion and Line Rebuilds
19 AEP Thermal AEP -T1, AEP -T2, AEP -T3, AEP -T4, AEP -T5 West Kingsport Line Cut In
909 AEP Thermal AEP -T43, AEP-T44, AEP-T45, AEP-T46 West Kingsport Transformer Replacement and Line Rebuilds
457 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Williams Grove - Allen 115 kV line upgrade sourced from Williams Grove 69 kV bus (FE-Allen Switchyard)
99 MetEd Voltage Drop, Voltage Magnitude N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-SVM16, N2-SVM17, N2-SVM18, N2-SVM19, N2-SVM26, N2-SVM27, N2-SVD3, N2-SVD4, N2-SVD5, N2-SVD6, N2-SVD7, N2-SVD8, N2-SVD9, N2-SVD10, N2-SVD11, N2-SVD12, N2-SVD15, N2-SVD16 Williams Grove - Allen 115 kV line upgrade sourced from Williams Grove 230 kV bus (FE-Allen Switchyard)
6 DOMINION GenDeliv GD-30 Line #2054 Rebuild - Charlottesville to Hollymeade Tap, 2-636 Option
26 DOMINION GenDeliv GD-30 Add 16 MW-64 MWh Battery Energy Storage System (BESS) at Hollymeade substation
38 DOMINION GenDeliv GD-30 Sleepy Hollow - Gordonsville 230kV Transmission Project
111 DOMINION GenDeliv GD-30 Charlottesville to Proffit 230 kV Greenfield Project
170 DOMINION GenDeliv GD-30 Add a 4.35 ohm series reactor at Hollymeade station on the terminal of Line 2054
182 DOMINION GenDeliv GD-30 Charlottesville to Gordonsville 230 kV Greenfield Project
268 DOMINION GenDeliv GD-30 Build a new 230 kV substation at Hollymeade Tap, rebuild 8.72 miles of line #2054 and 7.1 miles of line #2135
298 DOMINION GenDeliv GD-S12, GD-S17, GD-S30, GD-S715, GD-S37, GD-S717, N1-ST49 Greenfield Lee District Station
385 DOMINION GenDeliv GD-30 Charlottesville Rebuild and Greenfield Cismont Station
624 DOMINION GenDeliv GD-30 Line #2054 Rebuild - Charlottesville to Hollymeade Tap, 2-768.2 Option
100 Penelec Light Load Generation Deliverability and N-1 Thermal N1-LLT20, N1-LLT21, GD-LL45, GD-LL46 Install a new 230/115 kV transformer and associated facilities. Replace the Plant's 2B 115-17.2 kV transformer with a larger 230/17.2 kV transformer
306 Penelec Light Load Generation Deliverability and N-1 Thermal N1-LLT20, N1-LLT21, GD-LL45, GD-LL46 Replace the Shawville 2A 230/115-17.2 kV Transformer with a larger unit

Proposal ID Target Zone(s) Analysis Type Flowgates Comments
479 Dominion Thermal, GenDeliv N1-ST33,GD-S12,N2-ST2,N2-ST4,N2-ST5,N2-ST6,N2-ST7,N2-ST9,N2-ST11,N2-WT2,N2-WT3,DOM-T2 Line #2172 Reconductor - Brambleton to Evergreen Mills - Partial
26 Dominion Thermal, GenDeliv N1-ST33,GD-S12,N2-ST2,N2-ST4,N2-ST5,N2-ST6,N2-ST7,N2-ST9,N2-ST11,N2-WT2,N2-WT3,DOM-T2 Line #2172 - Reconductor Brambleton to Evergreen Mills - Full
740 Dominion Thermal, GenDeliv N1-ST32,GD-S11,N2-ST1,N2-ST3,N2-ST8,N2-ST10,N2-ST13,N2-ST14,N2-ST15,N2-WT1,N2-WT8,DOM-T1 Line #2210 Reconductor - Brambleton to Evergreen Mills - Partial Reconductor
735 Dominion Thermal, GenDeliv N1-ST32,GD-S11,N2-ST1,N2-ST3,N2-ST8,N2-ST10,N2-ST13,N2-ST14,N2-ST15,N2-WT1,N2-WT8,DOM-T1 Line #2210 Reconductor - Brambleton to Evergreen Mills - Full Reconductor
493 Dominion Thermal N2-ST12 Line #2213 Reconductor - Cabin Run to Yardley Ridge - Partial Reconductor
134 Dominion Thermal N2-ST12 Line #2213 Reconductor - Cabin Run to Yardley Ridge - Full Reconductor
704 Dominion Load Drop N2-SLD8,N2-WLD4 Waxpool Loop - Nimbus to Farmwell line extension
721 Dominion Thermal, GenDeliv, Load Drop GD-S11,GD-S12,N2-SLD,8N2-WT1,N2-WT2,N2-WT3,N2-WT8,N2-WLD4 Stonewater - Waxpool 230kV Transmission Project
575 ComEd GenDeliv GD-W3,GD-W4 Crete-St. John 345 kV Reconductoring Proposal
860 Dominion Load Drop N1-WLD-1,N1-WLD-2,N2-WLD5 Relieve 300 MW Load Drop on Line#219 and Line#2066 (winter N-1-1, Tower, and FB)
376 Dominion Load Drop N2-SLD8,N2-WLD4 Waxpool Loop - Loop Line #2031 Option
883 Dominion Load Drop N2-SLD8,N2-WLD4 Waxpool Loop - Shellhorn Option
173 ComEd GenDeliv GD-W3,GD-W4 Reconductor 345 kV Line 94507 Crete - St. John
573 ComEd GenDeliv GD-W3,GD-W4 Reconductor 345 kV Lines 6607 East Frankfort - Crete and 94507 Crete - St. John
148 ComEd GenDeliv GD-W3,GD-W4 Cedar Run - Cline 345kV Transmission Project
270 AEP Thermal AEP-T219,AEP-T221,AEP-T222,AEP-T223,AEP-T225,AEP-T226,AEP-T227,AEP-T228,AEP-T229,AEP-T230,AEP-T231,AEP-T232,AEP-T233,AEP-T234,AEP-T237,AEP-T238,AEP-T239,AEP-T240,AEP-T243,AEP-T244,AEP-T250 Birch Ridge - Natrium 138kV Transmission Project
494 BGE GenDeliv GD-S480,GD-S483 Pumphrey Transformer Replacement
281 ComEd GenDeliv GD-W3,GD-W4 Rebuild 345 kV double circuit Lines 94507 and 97008 Crete - St. John
354 ComEd GenDeliv GD-W3,GD-W4 Rebuild 345 kV Lines 6607/6608 East Frankfort - Crete and 94507/97008 Crete - St. John
241 ComEd GenDeliv GD-W3,GD-W4 Crete - St. John SmartValve
855 Dominion Voltage, Voltage and Magnitude N2-SVM52,N2-SVM53,N2-SVM54,N2-SVM55,N2-WVM15,N2-WVM16,N2-WVM17,N2-WVM18,N2-WVM19 Pierce Brook Substation, Install 2nd 345 kV Reactor
901 ComEd GenDeliv GD-W3,GD-W4 Install Series Inductor on Line 94507
763 BGE GenDeliv GD-S480,GD-S483 Erdman Reconfiguration
514 BGE GenDeliv GD-W3,GD-W4 Pumphrey-Graceton Transformer Replacement
420 BGE GenDeliv GD-W3,GD-W4 Constitution-Concord 110567/110568 Re-conductor - Partial 110563/110564 Re-conductor
836 BGE GenDeliv GD-W3,GD-W4 Constitution-Concord 110567/110568 Re-conductor - Partial 110563/110564 Re-conductor
179 AEP Thermal AEP-T356,AEP-T357,AEP-T358,AEP-T359,AEP-T360,AEP-T361,AEP-T362,AEP-T363,AEP-T364,AEP-T365 West New Philadelphia Breaker Installation
182 AEP Thermal AEP-T366,AEP-T367,AEP-T368,AEP-T373eft" Newcomerstown-Salt Fork Switch 69 kV Rebuild
109 AEP Thermal AEP-T366,AEP-T367,AEP-T368,AEP-T373 West Cambridge Transformer Addition
848 AEP Thermal AEP-T281,AEP-T284,AEP-T285,AEP-T286,AEP-T287,AEP-T288,AEP-T289,AEP-T290,AEP-T291,AEP-T292,AEP-T293,AEP-T298 Rockhill Circuit Switcher Install
503 AEP Thermal AEP-T168,AEP-T169,AEP-T170 Fremont Breaker and Bloom Road Cap Bank Installation
308 AEP Thermal AEP-T7,AEP-T8,AEP-T9,AEP-T10,AEP-T11,AEP-T220,AEP-T224,AEP-T235,AEP-T236,AEP-T241,AEP-T242,AEP-T245,AEP-T246,AEP-T247,AEP-T248,AEP-T249,AEP-T254,AEP-T255,AEP-T263,AEP-T264,AEP-T275,AEP-T276,AEP-T282,AEP-T283,AEP-T378,AEP-T379,AEP-T382,AEP-T383,AEP-T386,AEP-T387,AEP-T392,AEP-T393,AEP-T394,AEP-T395,AEP-T396,AEP-T397,AEP-T400,AEP-T401,AEP-T402,AEP-T408,AEP-T411,AEP-T417,AEP-T419,AEP-T420,AEP-T427,AEP-T428,AEP-T435,AEP-T436,AEP-T439,AEP-T440,AEP-T441,AEP-T461,AEP-T462,AEP-T463,AEP-T465 Dragoon Transformer and Line Addition
628 AEP Thermal AEP-T376,AEP-T377,AEP-T384,AEP-T385,AEP-T388,AEP-T389 Lancaster Area Switching Improvements
804 AEP Thermal, GenDeliv N1-ST41,N1-ST42,GD-S298,GD-S446,GD-S315,AEP-T219,AEP-T221,AEP-T222,AEP-T223,AEP-T225,AEP-T226,AEP-T227,AEP-T228,AEP-T229,AEP-T230,AEP-T231,AEP-T232,AEP-T233,AEP-T234,AEP-T237,AEP-T238,AEP-T239,AEP-T240,AEP-T243,AEP-T244,AEP-T250 Kammer-Natrium Upgrades
538 AEP GenDeliv N1-ST41,N1-ST42,GD-S298,GD-S446,GD-S315,AEP-T219,AEP-T221,AEP-T222,AEP-T223,AEP-T225,AEP-T226,AEP-T227,AEP-T228,AEP-T229,AEP-T230,AEP-T231,AEP-T232,AEP-T233,AEP-T234,AEP-T237,AEP-T238,AEP-T239,AEP-T240,AEP-T243,AEP-T244,AEP-T250 Natrium Area Line Reconfiguration
602 AEP Thermal AEP-T63,AEP-T70,AEP-T71,AEP-T72,AEP-T73,AEP-T66,AEP-T67,AEP-T64,AEP-T65,AEP-T68,AEP-T69 North Woodcock-East Leipsic 69 kV Line
957 AEP Thermal AEP-T63,AEP-T70,AEP-T71,AEP-T72,AEP-T73,AEP-T66,AEP-T67,AEP-T64,AEP-T65,AEP-T68,AEP-T69 East Leipsic-New Liberty 138 kV Conversion
915 AEP Thermal AEP-T376,AEP-T377,AEP-T384,AEP-T385,AEP-T388,AEP-T389 Lancaster Area Line Rebuilds
962 BGE GenDeliv GD-S480,GD-S483 Pumphrey Transformer, Constitution-Concord 110567/110568 Re-conductor, Partial 110563/110564 Re-conductor
191 BGE GenDeliv GD-S480,GD-S483 Pumphrey Transformer, Constitution-Concord 110567/110568 Concord-Monument Street 110563/110564 Re-conductor
393 ComEd GenDeliv GD-W3 Zebedee 345 kV Greenfield Station
235 ComEd GenDelive GD-W3 Goodenow-Lemon Lake 345kV Greenfield Line and Stations
317 AEP Thermal AEP-T70,AEP-T71,AEP-T72,AEP-T73,AEP-T69 Richlands to East Lepsic 138 kV
341 AEP Thermal AEP-T63,AEP-T70,AEP-T71,AEP-T72,AEP-T73,AEP-T66,AEP-T67,AEP-T64,AEP-T65,AEP-T68,AEP-T69 East Leipsic-Maroe 69kV Loop
608 AEP Thermal AEP-T68,AEP-T69,AEP-T70,AEP-T71,AEP-T72,AEP-T73 East Leipsic to Maroe 69 kV Single Circuit

Proposal ID Target Zone(s) Analysis Type Flowgates Comments
441 Dominion End of Life Criteria DOM-O5 Rebuild 500 kV Line #514 Goose Creek – Doubs(FE)

Proposal ID Target Zone(s) Analysis Type Flowgates Comments
697 AEP Thermal AEP-T431, AEP-T464, AEP-T475, AEP-T430, AEP-T474, AEP-T485, AEP-T473, AEP-T484, AEP-T472, AEP-T483, AEP-T471, AEP-T482, AEP-T470, AEP-T481, AEP-T480, AEP-T429, AEP-T469, AEP-T424, AEP-T479, AEP-T467, AEP-T478, AEP-T466, AEP-T477, AEP-T476 Mount Vernon Area Line Reconfiguration
860 AEP Thermal AEP-T431, AEP-T464, AEP-T475, AEP-T430, AEP-T474, AEP-T485, AEP-T473, AEP-T484, AEP-T472, AEP-T483, AEP-T471, AEP-T482, AEP-T470, AEP-T481, AEP-T480, AEP-T429, AEP-T469, AEP-T424, AEP-T479, AEP-T467, AEP-T478, AEP-T466, AEP-T477, AEP-T476 West Mount Vernon Area Rebuilds
533 AEP Thermal AEP-T431, AEP-T464, AEP-T475, AEP-T430, AEP-T474, AEP-T485, AEP-T473, AEP-T484, AEP-T472, AEP-T483, AEP-T471, AEP-T482, AEP-T470, AEP-T481, AEP-T480, AEP-T429, AEP-T469, AEP-T424, AEP-T479, AEP-T467, AEP-T478, AEP-T466, AEP-T477, AEP-T476 Wolf Run - Gambier - Martinsburg Transmission Project

Proposal ID Target Zone(s) Analysis Type Flowgates Comments
862 ATSI FERC 715 TO Criteria AMPT-01 Brewster Area Reliability Project
185 ATSI FERC 715 TO Criteria AMPT-01 Brewster Iron Man 96kV Transmission Project
20 ATSI, AEP FERC 715 TO Criteria AMPT-01 Brewster-Alpine 96kV Greenfield Line
991 ATSI, AEP FERC 715 TO Criteria AMPT-01 Brewster-E. Wilmot Greenfield 69 kV Line & Station
380 ATSI, AEP FERC 715 TO Criteria AMPT-01 Brewster-Pigeon Run Greenfield 69 kV Line & Station
74 ATSI FERC 715 TO Criteria AMPT-01 Brewster-Crossroads Greenfield Line and Station
978 ATSI FERC 715 TO Criteria AMPT-01 Brewster-Harmon 69 kV Parallel Line
839 ATSI FERC 715 TO Criteria AMPT-01 Harmon-Yager 138kV Greenfield Line
105 ATSI FERC 715 TO Criteria AMPT-01 Brewster Muni (Harmon) 69 kV - 2nd Source - Proposal #1
207 ATSI FERC 715 TO Criteria AMPT-01 Brewster Muni (Harmon) 69 kV - 2nd Source - Proposal #2
610 ATSI, AEP FERC 715 TO Criteria AMPT-01 Brewster Second Supply – Wilmot
595 ATSI, AEP FERC 715 TO Criteria AMPT-01 Brewster Second Supply – Beach City
373 ATSI FERC 715 TO Criteria AMPT-01 Brewster Second Supply – 138 kV

Proposal ID Target Zone(s) Analysis Type Flowgates Comments
574 ComEd Winter Generation Deliverability GD-W252, GD-W253, GD-W257, GD-W258 Install two (2) 765 kV circuit breakers at Wilton Center substation and move the Collins line exit to a new bus position
640 Dominion Summer N-1 & N-1-1 Themal, Gen Deliv Violations N1-ST46, GD-S5, GD-S7, N2-ST69, N2-ST70, N2-ST71 Increase the maximum operating temperature of 230 kV line 227
800 Dominion Summer N-1 & N-1-1 Themal, Gen Deliv Violations N1-ST46, GD-S5, GD-S7, N2-ST69, N2-ST70, N2-ST71 Reconductor 230 kV Line 227 between Pleasant View Junction and Beaumeade
418 Dominion Summer N-1 & N-1-1 Themal, Gen Deliv Violations N1-ST46, GD-S5, GD-S7, N2-ST69, N2-ST70, N2-ST71 Rebuild 230 kV Line 227 Cochran Mill DP - Pleasant View Junction and reconductor Pleasant View Junction - Beaumeade and Cochran Mill DP - Belmont
626 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Install a series reactor on the Silverside-Darley 69 kV line
820 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Install a SmartWire device in series with the Silverside-Darley 69 kV line
673 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Reconductor Silverside-Darley and Darley-Naamans 69 kV lines and upgrade terminal equipment
174 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Build a new 69 kV line Edge Moor-Claymont
36 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Build a new substation near Linwood Substation (PECO), build a in 230 kV line to Edge Moor and tap the Chichester-Linwood 230 kV Line (PECO).
522 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Build new 230 kV line Edge Moor-Chichester
637 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Build new substation near Linwood Substation (PECO), build a new 230 kV line to Harmony, and tap the Chichester-Linwood 230 kV Line (PECO).
839 DPL Summer & Winter Generation Deliverablity  GD-S537, GD-S538, GD-W441, GD-W442 Build a new 230 kV line Harmony-Chichester
702 APS Summer & Winter N-1-1 Voltage Violations  N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVD1, N2-WVD2, N2-WVD3, N2-WVD4, N2-WVD5, N2-WVD6, N2-WVD7, N2-WVD8, N2-WVD9, N2-WVD10 Reconfigure Stonewall 138 kV substation to a six-breaker breaker-and-a-half layout and install two (2) 36 MVAR capacitors
620 APS Summer & Winter N-1-1 Voltage Violations  N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVD1, N2-WVD2, N2-WVD3, N2-WVD4, N2-WVD5, N2-WVD6, N2-WVD7, N2-WVD8, N2-WVD9, N2-WVD10 Reconfigure Hampshire 138 kV switching station to a networked ring bus. Install one (1) 34.6 MVAR capacitor at Inwood
788 APS Summer & Winter N-1-1 Voltage Violations N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVD1, N2-WVD2, N2-WVD3, N2-WVD4, N2-WVD5, N2-WVD6, N2-WVD7, N2-WVD8, N2-WVD9, N2-WVD10 Build a new 500/138 kV station (Woodside) tapping Doubs-Bismark 500 kV, Stonewall-Feagan’s Mill 138 kV and Stonewall-Inwood 138 kV lines

Proposal ID Target Zone(s) Analysis Type Congestion Driver Major Component/Project Description
469 MetEd Market Efficiency ME-1 Install a SmartWires Device on the Lincoln - Hunterstown 115 kV line
293 MetEd Market Efficiency ME-1 Build a 4 position 115 kV ring bus (Meade) at Lincoln Tap Substation
398 MISO Market Efficiency ME-7 Build new 345 kV transmission line from the existing Meadow Lake station to a new 345 kV switching station called “Pike Creek".
249 MISO Market Efficiency ME-7 Install a 50 MW 4-hour battery at the existing Trail Creek 138 kV station.
129 MISO Market Efficiency ME-7 Build a new 138 kV Kuchar station on the Bosserman-Liquid Carbonics 138 kV line. Extend a new 138 kV single circuit transmission line from the Kuchar Station to the existing Luchtman Station.
436 MISO Market Efficiency ME-7 Build a new Toto 345 kV Switching Station and interconnect the existing Olive - Reynolds #1, Olive - Reynolds #2, and Schahfer - Burr Oak 345 kV transmission lines
481 MISO Market Efficiency ME-7 Reconductor Michigan City-Trail Creek-Bosserman (6.7 mile and 4.0 mile) and Maple – LNG 138 kV (7.8 mile) circuits.
322 AMIL Market Efficiency ME-6 Build a new 345 kV line between the Palmyra and Herleman Substations and rebuild the existing Palmyra – Marblehead 161 kV line and a Marblehead – Herleman 138 kV line.
506 AMIL Market Efficiency ME-6 Build a new 345 kV line between the Maywood and Herleman Substations and rebuild the existing Palmyra – Marblehead 161 kV line and a Marblehead – Herleman 138 kV line.
775 MISO Market Efficiency ME-2 Decouple part of multi-bundled conductor on a portion of Monroe-Wayne 345 kV line and re-utilize the adjacent Monroe-Coventry line.
078 MISO Market Efficiency ME-2 Decouple part of multi-bundled conductor on a portion of Monroe-Wayne 345 kV line.
782 MISO Market Efficiency ME-2 Upgrade the Monroe-Wayne 1&2 345 kV line rating by replacing switches at the 345 kV Wayne Station.
830 MetEd Market Efficiency ME-1 Build a 500/115 kV substation on Hunterstown-Conastone 500 kV line near Littlestown, PA. and build a 115 kV line from new station to Germantown station.
616 MetEd Market Efficiency ME-1 Build a 500/230 kV substation on Hunterstown-Conastone 500 kV line near Wentz, MD., build a 230 kV line from new substation to Carroll substation, install a 500/230 kV transformer Peach Bottom station, and build a Peach Bottom-Graceton 230 kV line.
593 MetEd Market Efficiency ME-1 Build a 500/115 kV substation on Hunterstown-Conastone 500 kV line near Littlestown, PA., build a 115 kV line from new substation to Germantown substation, install a 500/230 kV transformer at Peach Bottom, and build a Peach Bottom-Graceton 230 kV line.
387 MetEd Market Efficiency ME-1 Build a 500-230 kV substation on Hunterstown-Conastone 500 kV line near Wentz, MD. and build a 230 kV line from new substation to Carroll substation.
413 MetEd Market Efficiency ME-1 Build a 115 kV line from Hunterstown to Lincoln stations and install a 10 MW 2-hour battery at Lincoln.
402 MetEd Market Efficiency ME-1 Build a 115 kV line from Hunterstown to Lincoln stations and install a 25 MW 2-hour battery at Lincoln.
960 MetEd Market Efficiency ME-1 Build a 115 kV line from Hunterstown to Lincoln substations.
868 MetEd Market Efficiency ME-1 Build a 500 kV switchyard on the PEBO-DELT 500 kV line and install a new 115 kV ring bus at the Orrtanna tap point of the METED Hunterstown – Orrtanna – Lincoln 115 kV line.
453 MetEd Market Efficiency ME-1 Install a 25 MW 4-hour battery at Lincoln 115 kV station.
201 MetEd Market Efficiency ME-1 Install a 25 MW 2-hour battery at Lincoln 115 kV station.
892 MetEd Market Efficiency ME-1 Install a 50 MW 2-hour battery at Lincoln 115 kV station.
647 MetEd Market Efficiency ME-1 Install a 115 kV ring bus at the Orrtanna tap point of the METED Hunterstown – Orrtanna – Lincoln 115 kV line, build an Otter Creek 500/230 kV station, and rebuild 1.3 miles of Manor – Graceton 230 kV line.
511 MetEd Market Efficiency ME-1 Install a 115 kV ring bus at the Orrtanna tap point of the METED Hunterstown – Orrtanna – Lincoln 115 kV line and build an Otter Creek 500/230 kV substation.
007 MetEd Market Efficiency ME-1 Install a 115 kV ring bus at the Orrtanna tap point of the METED Hunterstown – Orrtanna – Lincoln 115 kV line.
034 MetEd Market Efficiency ME-1 Rebuild the Hunterstown – Lincoln - Germantown 115 kV and Germantown - Carrol 138 kV lines as double circuit 230 kV line.
622 MetEd Market Efficiency ME-1 Rebuild the Hunterstown - Lincoln 115 kV line.
021 MetEd Market Efficiency ME-1 Rebuild the Hunterstown-Lincoln 115 kV line, build a Peach Bottom - Graceton 230 kV circuit, upgrade the existing Face Rock 115/69 kV transformers and circuit switching at Rice and Ringgold 230 kV stations.
389 MetEd Market Efficiency ME-1 Rebuild the Hunterstown-Lincoln 115 kV line, add a Peach Bottom 500/230 kV transformer, and add a Peach Bottom-Graceton 230 kV line.
357 MetEd Market Efficiency ME-1 Build a 500/230 kV substation on the Delta - Peach Bottom 500 kV line, build a 230 kV line from the new station to Graceton, build a 230 kV switching station on the Carroll - Mt. Airy 230 kV line, and build a 230 kV line from the new station to Hunterstown.
847 MetEd Market Efficiency ME-1 Build a 500/230 kV substation on the Delta - Peach Bottom 500 kV line, build a 230 kV line from the new station to Graceton and reconductor the Hunterstown - Lincoln 115 kV line.

Proposal ID Proposing Entity Target Zone(s) Analysis Type FG# Major Component/Project Description
1A DEOK DEOK Summer N-1 Load Drop N1-SLD1 Add redundant relaying to Port Union 138kV Bus 2 to eliminate the contingency driving the reliability criteria violation.
2A Dominion Dominion Summer N-1 High Voltage N1-SVH1, N1-SVH2 This is an operational solution that will remotely open Davis TX#1 breaker L122, immediately following the breaker-failure event (2036T2142) at Radnor Substation thus resolving the post contingency high voltage.
2B Dominion Dominion Summer N-1 High Voltage N1-SVH1, N1-SVH2 Move the existing 230/69kV TX#4 to the vacant 230/69kV TX#2 spot at Davis Substation.
2C Dominion Dominion Summer N-1 High Voltage N1-SVH1, N1-SVH2 Move spare 230/69kV transformer from Jefferson Street Substation to the vacant Transformer #2 bay at Davis Substation.
2D Dominion Dominion Summer N-1 High Voltage N1-SVH1, N1-SVH2 Construct a 230kV four (4) breaker GIS ring bus in Davis Substation and terminate existing Line 2037 and Line 2121.
2E Dominion Dominion Summer N-1 High Voltage N1-SVH1, N1-SVH2 Install a 50 MVAR fixed shunt reactor at Davis Substation on the 69kV bus.
2F Dominion Dominion Summer N-1 High Voltage N1-SVH1, N1-SVH2 A new substation called Cloverleaf with a 230kV variable shunt reactor with a new 230kV underground line roughly 300 ft extending from Cloverleaf Substation to Davis substation terminating at the 230kV bus.

AEP

Date
2017_1-8B - Maddox-Southwest_Lima_345kV PDF
3.1.2018

Duquesne

Date
2017_1-4A - Cheswick-Plum_138kV PDF
3.1.2018

Exelon

Date
2017_1-9D - Edge_Moor-Chichester_230kV PDF
3.1.2018
2017_1-9E - Edge_Moor-Linwood_230kV PDF
3.1.2018
2017_1-9F - Edge_Moor-Post_230kV PDF
 3.1.2018
2017_1-9G - Edge_Moor-New_PECO_sub_230kV PDF
 3.1.2018
2017_1-9H - Harmony-Linwood_230kV PDF
 3.1.2018
2017_1-9I - Harmony-Chichester_230kV PDF
 3.1.2018
2017_1-9J - Harmony-Clay_230kV PDF
3.1.2018
2017_1-9N - Edge_Moor-Pedrick_230kV PDF
3.1.2018

First Energy

Date
2017_1-10F - Bunola_Substation_138kV PDF 
3.1.2018

Nextera

Date
2017_1-5A - Lamberts_Run_500-138kV_Sub PDF
3.1.2018
2017_1-5B - Miracle_138kV_Series Reactor PDF
 3.1.2018
2017_1-5C - Miracle_138kV_Reconductor PDF
 3.1.2018

NTD

Date
2017_1-2A - Glade_Run-Waldo_Run_138kV PDF
3.1.2018
2017_1-2B - Logans_Ferry-Pucketa_138kV PDF
 3.1.2018
2017_1-2C - Logans_Ferry-Pucketa_138kV PDF
 3.1.2018
2017_1-2D - Logans_Ferry-Thorn_Run_345kV PDF
 3.1.2018
2017_1-2E - Twelvemile_345kV_Sub PDF
 3.1.2018

PSEG

Date
2017_1-3A - Beaver_Run-Logans_Ferry_500kV PDF
 3.1.2018

Transource

Date
2017_1-7A - Barking_Road-Wright_Road_138 kV PDF
3.1.2018
2017_1-7B - Anson_Station_345kV PDF
3.1.2018
2017_1-7C - Sycolin_Creek_230kV PDF
3.1.2018
2017_1-7D - York-Coyote_345kV PDF
3.1.2018
2017_1-7E - Narrow_Run-Waldo_Run_500 kV PDF
 3.1.2018
2017_1-7F - Tanners_Creek-Miami_Fort_345kV PDF
3.1.2018
2017_1-7G - Upper_Harmony-McCalmont_138kV PDF
3.1.2018

Dominion

Date
1-8Q - Palmyra 500kV Capacitor PDF
2.27.2017

Nipsco

Date
1-9A - Bosserman Reconductor PDF
2.25.2017
1-9B - Thayer Morrison 138kV PDF 
2.28.2017

Nextera

Date
1-10A - Spring Hill 500-230kV PDF 
2.28.2017
1-10B - Rolling Prairie 345-138kV PDF 
2.28.2017
1-10C - Rowland-Perryman 230kV PDF
2.28.2017
1-10D - Rowland-Perryman 230kV Pylesville 500-230kV PDF
2.28.2017
1-10E - Perryman-Rowland-Pylesville 230kV Pylesville 500-230kV PDF
 2.28.2017

AEP-Nipsco

Date
1-12D - Olive-Liquid Carbonics 138kV PDF
3.2.2017

Transource

Date
1-13A - Baldwin Road-Raphael Road 230kV PDF
2.28.2017
1-13B - Conastone-Dulaney Valley 230kV PDF 
2.28.2017
1-13C - Conastone-Long Green 230kV PDF
 2.28.2017
1-13D - Conastone-Long Green-Raphael Road 230kV PDF
 2.28.2017
1-13E - Hereford-Dulaney Valley 230kV PDF
 2.28.2017
1-13F - Love Run-Perryman 230kV PDF
2.28.2017
1-13H - York Coyote 345kV PDF
2.28.2017

DATC

Date
1-14A - Furnace Run-Perryman PDF
2.28.2017

PPL-ATXI East

Date
1-15A -  Conastone-Graceton-Bagley with Conastone-Baldwin 230kV PDF
2.28.2017
1-15B -  Conastone-Graceton-Bagley with Peach Bottom-Otter Point 230kV PDF
2.28.2017

PSEG

Date
1-16A - Peach Bottom-Otter Point 230kV PDF
2.28.2017
1-16B - PeachBottom-Raphael Road 230kV PDF
3.1.2017
1-16C - Conastone-Raphael Road 230kV PDF
3.1.2017
1-16D - Conastone-Northeast 230kV PDF
3.1.2017
1-16E - Peach Bottom-Northeast 230kV PDF
 3.1.2017

Exelon

Date
1-17A - AEP-Public-Cottage Grove PDF
2.28.2017
1-17B - Meadow Lake-Pike Creek 345kV PDF
 2.28.2017

NTD

Date
1-18A - Baltimore 2 PDF
3.1.2017
1-18B - Baltimore 3 PDF
3.1.2017
1-18C - Baltimore 5 PDF
 3.1.2017
1-18D - Baltimore 6 PDF
 3.1.2017
1-18F - Conastone-Fitzhugh Run PDF
 3.1.2017
1-18G - Fells Creek PDF
 3.1.2017
1-18H - Green Ridge 230kV PDF
 3.1.2017
1-18I - Green Ridge 500kV PDF
 3.1.2017
1-18J - Hunterstown-GreenValley PDF
 3.1.2017
1-18K - James Creek PDF
 3.1.2017
1-18L - Limestone Ridge PDF
 3.1.2017
1-18M - Marysville-Miami_Spring Run-Crown PDF
 3.1.2017
1-18N - Marysville-Miami PDF
 3.1.2017
1-18O - Smith Branch PDF
 3.1.2017
1-18P - Spring Run-Crown PDF
 3.1.2017
1-18Q - Trexler Run-Harwood PDF
 3.1.2017
1-18R - Turkey Creek PDF
 3.1.2017
1-18S - Coffee Creek PDF
 3.1.2017

ITC

Date
1-20A - Peach Bottom-Old Post 230kV PDF
3.2.2017
1-20B - Conastone-Raphael 230kV PDF
3.2.2017
1-20C - Conastone-Northeast 230kV PDF
3.2.2017
1-20D - Conastone-Old Post 230kV PDF
3.2.2017
1-20E - Peach Bottom-Pyle-Fallston-Old Post 230kV PDF
 3.2.2017
1-20F - Conastone-Pyle-Fallston-Old Post 230kV PDF
3.2.2017
1-20G - Peach Bottom-Northeast 230kV PDF
3.2.2017
1-20H - Peach Bottom-OldPost 230kV+Battery PDF
3.2.2017
1-20I - Peach Bottom-Pyle-Fallston-OldPost 230kV+battery PDF
3.2.2017


Date
DEOK / AEP Competitive Cluster Independent Constructability Review White Paper PDF
1.11.2017

Redacted Public Greenfield Proposals

Transource

Date
2016_2-3B - Version Homer City-Two Lick Creek PDF
10.17.2016
2016_2-3C - Russ 345_138 kV Station PDF
10.17.2016
2016_2-3D - Upper Harmony-McCalmont 138 PDF 10.17.2016
2016_2-3E - Williams Grove 115 PDF 10.17.2016
2016_2-3F - York-Coyote 345 PDF 10.17.2016

Nextera

Date
2016_2-6A - Salem345-138kV PDF
10.17.2016
2016_2-6B - DE 345 KV Trans PDF
10.17.2016

AEP

Date
2016_2-7I - Dequine-Meadow Lake 345 PDF
10.17.2016
2016_2-7M - Eugene-Dequine 345 kV SGL 2 PDF
10.17.2016
2016_2-7P - Eugene-Meadow Lake 345 kV SGL PDF 10.17.2016

Northeast Transmission Development

Date
2016_2-9A PDF
10.17.2016
2016_2-9B PDF
10.17.2016
2016_2-9C PDF
10.17.2016
2016_2-9D PDF 10.17.2016
2016_2-9F PDF 10.17.2016
2016_2-9G PDF 10.17.2016
2016_2-9I PDF 10.17.2016
2016_2-9J PDF 10.17.2016
2016_2-9O PDF 10.17.2016
2016_2-9P PDF 10.17.2016
2016_2-9Q PDF 10.17.2016
2016_2-9R PDF 10.17.2016
2016_2-9S PDF 10.17.2016
2016_2-9T PDF 10.17.2016
2016_2-9V PDF 10.17.2016

Mid-Atlantic MCN

Date
2016_2-10B PDF
10.17.2016

PSEG

Date
2016_2-11C - Vectren Eugene to Meadow Lake 345kV PDF
10.17.2016
2016_2-11D - Vectren Ghent to East Bend 345kV PDF
10.17.2016
2016_2-11E - Vectren Clifty Creek to East Bend 345kV PDF 10.17.2016

PPL

Date
2016_2-13F - PPL - Public Redacted Version - Clifty_Madison PDF
10.17.2016
2016_2-13G - PPL - Public Redacted Version - Dequine_New_Line PDF
10.17.2016
2016_2-13I - PPL - Public Redacted Version - TodhunterRockiesExp PDF 10.17.2016
2016_2-13J - PPL - Public Redacted Version - Nickel_Warren PDF 10.17.2016



AEP

Date
2-3A PDF
10.30.2015
2-3C PDF
10.28.2015
2-3D PDF 
10.28.2015
2-3E-3F PDF
10.28.2015
2-3G-3H PDF
10.28.2015
2-3I PDF 
10.30.2015
2-3J PDF 
10.30.2015

Northeast Transmission Development

Date
2-2A-2I PDF
10.28.2015


Dominion

Date
2015_1-1C - Carson-Rogers Rd 500kV PDF
9.8.2015
2015_1-1D - Carson-Rawlings 500kV PDF 
9.8.2015
2015_1-1E - Rogers Road-Maclins 500kV Ln and Maclins-Clubhouse 230kV PDF
9.8.2015
2015_1-1F - Rawlings-Purdy 230kV PDF
9.8.2015

AEP

Date
2015_1-2D - Clinch River-Keen Mountain PDF 
9.11.2015
2015_1-2E - Clinch River-Beaver Creek PDF 
9.11.2015
2015_1-2G - Dequine-Meadow Lake 345 Ckt3 PDF
9.10.2015
2015_1-2L - Herlan-Blue Racer 138kV PDF
9.11.2015

Transource

Date
2015_1-5A - Anson 345 kV Station PDF
9.8.2015
2015_1-5B - Burma-Piney 115kV PDF 
9.8.2015
2015_1-5C - Cambria 500 115 kV Station Project PDF
9.8.2015
2015_1-5D - Carlisle Pike-Fayetteville 138kV PDF 
9.8.2015
2015_1-5E - Carlisle Pike-Rice Project PDF
9.8.2015
2015_1-5F - Carson Rawlings 500 kV Project PDF 
9.8.2015
2015_1-5G - Tanners Creek-Miami Fort PDF 
9.8.2015

Nextera

Date
2015_1-6A - Rogers Road to Pleasant Shade & Carson to Rawlings PDF
9.8.2015
2015_1-6B - Carson to Rawlings PDF 
9.8.2015
2015_1-6C - Carson to Rogers Road PDF 
9.8.2015

PSEG

Date
2015_1-7A - Dequine to Meadow 345kV PDF
9.8.2015
2015_1-7B - Englishtown to East Windsor 230kV PDF 
9.8.2015
2015_1-7C - Englishtown 500 230kV PDF
9.8.2015
2015_1-7D - Brunswick-Wake 500230 kV New Line Clubhouse 230kV PDF
9.8.2015
2015_1-7E - Beaver to Black River 138kV PDF 
9.8.2015
2015_1-7F - Beaver to Lake Ave 138kV PDF 
9.8.2015
2015_1-7G - Station Beaver 138 69kV to New Station Sheffield 138kV PDF
9.8.2015
2015_1-7H - Guyandotte to Tams Mountain 138kV PDF 
9.8.2015
2015_1-7I - Matt Funk-Kanawha River 345 138kV PDF 
9.8.2015
2015_1-7J - Crossland to Elwood 138kV PDF
9.8.2015
2015_1-7K - Dowling to Bowling Green 5 138kV PDF 
9.8.2015

Northeast Transmission Development

Date
2015_1-8A-AD PDF
9.8.2015

ITC

Date
2015_1-9A-E PDF
9.8.2015


Transource

Date
2014_2B-1A - Cumberland Tap 1 PDF
3.17.2015
2014_2B-1B - Cumberland Tap 3 PDF
3.17.2015

Northeast Transmission Development

Date
2014_2B-3A PDF
3.17.2015
2014_2B-3B PDF
3.17.2015
2014_2B-3C PDF
3.17.2015
2014_2B-3D PDF 
3.17.2015
2014_2B-3E PDF 
3.17.2015
2014_2B-3F PDF 
3.17.2015

PPL/First Energy

Date
2014_2B-4A - Allen Williams Grove PDF
3.17.2015


Date
Independent Cost Review White Paper PDF
5.6.2016

Long-Term Public Redacted Proposals

Window closed on 2.27.2015

PPL

Date
201415_1-2C - AP South PDF
3.24.2015

AEP

Date
201415_1-4A - Gavin Kyger PDF
3.24.2015
201415_1-4H - Dequine-Meadow Lake 345 PDF
3.24.2015

Dominion

Date
201415_1-6D - Palmyra 500kV PDF
3.24.2015

Transource

Date
201415_1-7A - Axton EastDanville 230kV PDF
3.24.2015
201415_1-7B - Meadowbrook Doubs PDF 
3.24.2015
201415_1-7C - Meadowbrook Doubs 500kV PDF
3.24.2015

Dominion/Transource

Date
201415_1-8A - Joshua Falls Palmyra 765kV PDF
3.24.2015
201415_1-8B - Joshua Falls Palmyra 500kV PDF
3.24.2015
201415_1-8C - Axton Clover 765kV PDF 
3.24.2015
201415_1-8D - Axton Clover 500kV PDF 
3.24.2015
201415_1-8E - Joshua Falls to Farmville Single 230 kV PDF
3.24.2015
201415_1-8F - Joshua Falls to Farmville Double 230 kV PDF
3.24.2015

Dominion High Voltage

Date
201415_1-9A - Southern PA PDF
3.24.2015

ComEd

Date
201415_1-10C - Loretto Wilton Center PDF
3.24.2015

PECO

Date
201415_1-11A - Proposal 1 PDF
9.15.2015
201415_1-11B - Proposal 2 PDF
9.15.2015
201415_1-11C - Proposal 3 PDF
9.15.2015
201415_1-11D - Proposal 4 PDF
9.15.2015

DATC

Date
201415_1-14A - AP South PDF
3.24.2015
201415_1-14B - Germantown Fairview PDF
3.24.2015
201415_1-14C - Kentucky Substation PDF 
3.24.2015

GridAmerica

Date
201415_1-15A - NJMEP PDF
3.24.2015

Nipsco

Date
201415_1-16A - Wilton Center Reynolds Gwynneville PDF
3.24.2015
201415_1-16B - Pontiac Reynolds PDF 
3.24.2015

NextEra

Date
201415_1-17A - 1A PDF
3.24.2015
201415_1-17B - 1B PDF
3.24.2015
201415_1-17C - NextEra - 1C PDF
3.24.2015
201415_1-17D - 1D PDF
3.24.2015
201415_1-17E- 2A PDF
3.24.2015
201415_1-17F- 2B PDF
3.24.2015
201415_1-17G - 2C PDF
3.24.2015

First Energy

Date
201415_1-18E - AP South PDF
3.24.2015

Northeast Transmission Development

Date
201415_1-19A PDF
3.24.2015
201415_1-19B PDF
3.24.2015
201415_1-19C PDF
3.24.2015
201415_1-19D PDF
3.24.2015
201415_1-19E PDF
3.24.2015
201415_1-19F PDF
3.24.2015
201415_1-19G PDF
3.24.2015
201415_1-19H PDF
3.24.2015
201415_1-19I PDF
3.24.2015

ITC

Date
201415_1-20A - 3-1 PDF
3.24.2015
201415_1-20B - 3-3 PDF
3.24.2015
201415_1-20C - 3-4 PDF 
3.24.2015
201415_1-20D - 3-5 PDF 
3.24.2015
201415_1-20E - 3-6 PDF 
3.24.2015
201415_1-20F - 3-7 PDF 
3.24.2015
201415_1-20G - 3-9 PDF 
3.24.2015
201415_1-20H - 3-10 PDF
3.24.2015
201415_1-20I - 3-11 PDF 
3.24.2015
201415_1-20J - 3-1 PDF 
3.24.2015
201415_1-20K - 3-9 PDF 
3.24.2015
201415_1-20L - 3-1 PDF 
3.24.2015
201415_1-20M - 3-1 PDF 
3.24.2015
201415_1-20N - 3-9 PDF 
3.24.2015
201415_1-20O - 3-9 PDF 
3.24.2015

PSEG

Date
201415_1-21A - Eagle Point to Penrose 230kV PDF
3.24.2015
201415_1-21B - Gloucester Cuthbert 230kV PDF 
3.24.2015
201415_1-21C - Miami Fort to Willey 138kV PDF 
3.24.2015
201415_1-21D -Milford Cool Spring 230kV PDF 
3.24.2015
201415_1-21E - Reconductor Red Lion Cedar Creek PDF
3.24.2015
201415_1-21F - Red Lion Cedar Creek 230kV PDF 
3.24.2015

Ameren

Date
201415_1-22A - AP South & AEP - DOM Congestion PDF
3.24.2015
201415_1-22B - AP South & AEP - DOM Congestion PDF
3.24.2015
201415_1-22C - Taneytown - Carroll PDF 
3.24.2015
201415_1-22D - Miami Ft Willey PDF 
3.24.2015
201415_1-22E - Miami Ft Willey PDF 
3.24.2015
201415_1-22F - Miami Ft Willey PDF 
3.24.2015


PPL/First Energy

Date
2014 2A-1A - Allen Williams Grove PDF
2.17.2015

Transource

Date
2014 2A-2A - Cumberland Tap 1 PDF
2.17.2015
2014 2A-2A - Cumberland Tap 3 PDF
2.17.2015

Northeast Transmission Development

Date
2014 2A-3A - Dogwood Run PDF
2.17.2015


AEP

Date
2014_2-2K - Boone Area PDF
1.14.2015
2014_2-2Q - Belva - Clendenin 138kV PDF
1.14.2015
2014_2-2R - Therofare - Ivydale 138kV PDF
1.14.2015
2014_2-2S - Therofare - 138kV Tap PDF
1.14.2015
2014_2-2U - Skin Fork Area Improvements PDF 
1.14.2015
2014 2-2W - Bellaire-Glencoe-Herlan 138 kV PDF
1.14.2015
2014_2-2Y - Colfax-Drewrys PDF
1.14.2015

Transource

Date
2014_2-3A - Cumberland Tap PDF
12.16.2014
2014_2-3B - Sewaren Tap PDF
12.16.2014

First Energy

Date
2014_2-4E - Allen 230-115 kV PDF
12.16.2014

PECO

Date
2014_2-5A - Proposal 1 PDF 
1.14.2015
2014_2-5B - Proposal 2 PDF
1.14.2015

ITC Mid Atlantic

Date
2014_2-6A - Emilie to Mercer PDF
12.16.2014
2014_2-6B - Gordonsville Fairground Remington - Pratts PDF
1.12.2015

Northeast Transmission Development

Date
2014_2-7A - Cedar Plains PDF
12.16.2014
2014_2-7B - Dogwood Run PDF
12.16.2014
2014_2-7C - South Fork PDF
12.16.2014
2014_2-7D - Pratts PDF 
1.12.2015
2014_2-7E - Pratts PDF 
1.12.2015
2014_2-7F - Pratts PDF 
1.12.2015
2014_2-7G - Pratts PDF
1.12.2015
2014_2-7H - Pratts PDF 
1.12.2015
2014_2-7I - Pratts PDF
1.12.2015
2014_2-7J - Pratts PDF 
1.12.2015
2014_2-7K - Pratts PDF 
1.12.2015

Comed

Date
2014_2-8E - Schauff Road to Rock Falls PDF
12.16.2014

Nextera Energy Transmission

Date
2014_2-10A - DOM 5A PDF
1.14.2015
2014_2-10B - DOM 5B PDF
1.14.2015

NIPSCO

Date
2014_2-12A - Oglesby Pontiac Reynolds PDF
12.16.2014

Dominion/First Energy

Date
2014_2-13A - Pratts PDF
1.12.2015
2014_2-13B - Pratts PDF
1.12.2015
2014_2-13C - Pratts PDF
1.12.2015
2014_2-13D - Pratts PDF
2.23.2015

Ameren

Date
2014_2-14A - Option 1 - Pratts PDF
1.14.2015
2014_2-14B - Option 2 - Pratts PDF
1.14.2015
2014_2-14C - Option 3 - Pratts PDF
1.14.2015


Duke Energy
Date
2014-1-1B - Miami Fort to Willey New Branch PDF
9.30.2014
AEP
Date
2014-1-2G - Clinch River-Keen Mountain PDF
9.30.2014
2014-1-2H - Clinch River-Beaver Creek PDF
9.30.2014
2014-1-2L - Kyger Creek - Gavin 345-138 PDF
9.30.2014
Transource
Date
2014-1-3A - Brooke County PDF
9.30.2014
2014-1-3B - Lorain PDF
9.30.2014
2014-1-3C - Lorain Juniper PDF
9.30.2014
2014-1-3D - Lockwood Road-Stryker PDF
9.30.2014
2014-1-3E - Bryan-Stryker PDF
9.30.2014
2014-1-3F - Fremont-Hayes PDF
9.30.2014
2014-1-3G - West Fremont Hayes PDF
9.30.2014
2014-1-3H - Southwest Ohio PDF
9.30.2014
2014-1-3I - Montour PDF
9.30.2014
2014-1-3J - Crescent PDF
9.30.2014
2014-1-3K - Dresden PDF
9.30.2014
2014-1-3L - South Philly PDF
9.30.2014
Dominion High Voltage Mid-Atlantic
Date
2014-1-4C - Sunbury Susquehanna Montour Columbia Frackville PDF
9.30.2014
PPL
Date
2014-1-7A - AE 1 PDF
9.30.2014
2014-1-7B - AE 2 PDF
9.30.2014
2014-1-7C - AE 3 PDF
9.30.2014
2014-1-7D - AE 4 PDF
9.30.2014
2014-1-7E - AEP 1 PDF
9.30.2014
2014-1-7F - AEP 2 PDF
9.30.2014
2014-1-7G - FE 1 PDF
9.30.2014
2014-1-7H - FE 2 PDF
9.30.2014
2014-1-7K - PPL 3 PDF
9.30.2014
2014-1-7L - PPL 4 PDF
9.30.2014
2014-1-7M - PPL 5A PDF
9.30.2014
2014-1-7N - PPL 5B PDF
9.30.2014
2014-1-7O - PPL 6 PDF
9.30.2014
2014-1-7P - Project Compass PDF
9.30.2014
ITC
Date
2014-1-11A - 1-1 PDF
9.30.2014
2014-1-11B - 1-2 PDF
9.30.2014
2014-1-11C - 1-3 PDF
9.30.2014
2014-1-11D - 1-4 PDF
9.30.2014
2014-1-11E - 1-5 PDF
9.30.2014
2014-1-11F - 1-6 PDF
9.30.2014
PHI
Date
2014-1-12A - DPL PDF
9.30.2014
Nextera
Date
2014-1-13A - Meshoppen to Lackawanna PDF
9.30.2014
2014-1-13B - Montour to Sunbury PDF
9.30.2014
Northeast Transmission Development
Date
2014-1-14A - Crows Run PDF
9.30.2014
2014-1-14B - Delco to Eddystone PDF
9.30.2014
2014-1-14C - Garrison Run PDF
9.30.2014
2014-1-14D - Kammer To Holloway PDF
9.30.2014
2014-1-14E & E1 - Montour To Furman PDF
9.30.2014
2014-1-14F - Paddys Run PDF
9.30.2014
2014-1-14G - Tidd To Windsor PDF
9.30.2014
2014-1-14H & H1 - Clinch River to West Fork PDF
9.30.2014
2014-1-14I - BL England to Cardiff PDF
9.30.2014
2014-1-14J and J1 - Swisher Hill PDF
9.30.2014
2014-1-14K - Lake Avenue to Case PDF
9.30.2014
PSEG
Date
2014-1-15A - B.L. England to Cardiff 138kV PDF
9.30.2014
2014-1-15B - B.L. England to Cardiff 230kV PDF
9.30.2014
2014-1-15C - Dennis to B.L. England to Cardiff 230kV PDF
9.30.2014
2014-1-15D - Eagle Point to Penrose 230kV PDF
9.30.2014
2014-1-15E - Gloucester to Cuthbert Blvd 230kV PDF
9.30.2014
2014-1-15F - Kyger Creek - New Station 345kV PDF
9.30.2014


 

Window closed on 06.28.2013

Supplemental Responses

Dominion High Voltage (2013-1-1A)
Date
Dominion High Voltage (2013-1-1C)
 
Transource (2013-1-2B)
 

Northeast Transmission Development (2013-1-5A)

 

PSEG (2013-1-7K)

 
Notice PDF
9.24.2014

Redacted Public Proposals

Constructability Reports
Date
Constructability Analysis for the Dominion 1A Project PDF 
12.12.2014
Permitting Analysis for the Finalist Line Projects PDF
10.9.2014